Data record tests.capacitance-measurement.equipment.capacitor.maintenance

Verified 2026-10-13 Confidence: Medium

Provenance pending: the source of this record has not yet been confirmed as official.

Capacitance Measurement is specified for capacitors in maintenance testing at clause 7.20.1.B.3 of ANSI/NETA MTS-2023.

Value: capacitors

ProvenanceANSI/NETA MTS-2023 supports data record tests.capacitance-measurement.equipment.capacitor.maintenance, which is cited on the entry Capacitance Measurement.SOURCEANSI/NETA MTS-2023ANSI/NETA MTS-2023Licensed standard, clause 7.20.1.B.3DATA RECORDtests.capacitance-measurement.equipment.capacitor.maintenancetests.capacitance-measur..Verified 2026-10-13ENTRYCapacitance MeasurementCapacitance MeasurementNo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/NETA MTS-2023Licensed standard, clause 7.20.1.B.3
Data recordtests.capacitance-measurement.equipment.capacitor.maintenanceVerified 2026-10-13
EntryCapacitance MeasurementNo revisions
Subject
Capacitance Measurement (Test methods)
Kind
Equipment fact
Source
ANSI/NETA MTS-2023, clause 7.20.1.B.3, Maintenance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA MTS-2023Publisher information page
Also stated in
  • TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 13-12.b, PDF page 146, printed 13-3 (29 November 1996).
    Read the reference passage

    13-12.b. After being in service tests

    "These tests are only necessary in determining the operating condition of a power capacitor after exposure to possible damage or other trouble indications. The dielectric strength may be measured by applying the same voltage as given for the before service test. The capacitance can be determined by applying a known voltage and frequency of a good wave shape. Short-circuited or open-circuited capacitors will be indicated by this test."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 13-12.b, PDF page 146, printed 13-3, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

  • Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 13-13.b, PDF page 146, printed 13-3, item (1)(b) (29 November 1996).
    Read the reference passage

    13-13.b(1)(b). Interpretation

    "Blowing of the fuse indicates a short-circuited capacitor. Absence of current indicates an open-circuited capacitor. Good capacitors should have current readings of 100 to 115 percent of rated value, with the case and internal temperature at 25 degrees C. Current readings above 115 percent of rated current may indicate an internal short or the presence of harmonics in the test voltage."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 13-13.b, PDF page 146, printed 13-3, item (1)(b), 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-13created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.capacitance-measurement.equipment.capacitor.maintenance." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/data/tests.capacitance-measurement.equipment.capacitor.maintenance/.
Electrical Testing Reference, Data record tests.capacitance-measurement.equipment.capacitor.maintenance (Oct. 13, 2026), https://www.electricaltestingreference.com/data/tests.capacitance-measurement.equipment.capacitor.maintenance/.
@misc{etr-data-tests-capacitance-measurement-equipment-capacitor-maintenance,
  title = {Data record tests.capacitance-measurement.equipment.capacitor.maintenance},
  howpublished = {\url{https://www.electricaltestingreference.com/data/tests.capacitance-measurement.equipment.capacitor.maintenance/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {last substantive change 2026-10-13}
}
{{cite web |title=Data record tests.capacitance-measurement.equipment.capacitor.maintenance |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/data/tests.capacitance-measurement.equipment.capacitor.maintenance/ |date=2026-10-13 |access-date=}}