Data record tests.insulation-resistance.definition

Verified 2026-10-13 Confidence: High

IEEE 43-2013 treats insulation resistance as the quotient of a direct voltage applied across the insulation and the current that the voltage drives through it, read at a stated time after the voltage is applied.

ProvenanceIEEE 43-2013 supports data record tests.insulation-resistance.definition, which is cited on the entry Insulation Resistance.SOURCEIEEE 43-2013IEEE 43-2013Licensed standard, clause 9.2DATA RECORDtests.insulation-resistance.definitiontests.insulation-resista..Verified 2026-10-13ENTRYInsulation ResistanceInsulation Resistance1 revision
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceIEEE 43-2013Licensed standard, clause 9.2
Data recordtests.insulation-resistance.definitionVerified 2026-10-13
EntryInsulation Resistance1 revision
Subject
Insulation Resistance (Test methods)
Kind
Definition
Source
IEEE 43-2013, clause 9.2, Recommended Practice for Testing Insulation Resistance of Electric Machinery, IEEE. Publisher page for IEEE 43-2013Publisher information page
Also stated in
  • FIST 4-7, section 6.1.28, page 83 (August 2023).
    Read the reference passage

    6.1.28 Generator and Large Motor Windings

    "Insulation resistance is defined as the ratio of the applied direct voltage over the measured current. For typical stator winding insulation, an applied step-voltage will result in a measured current that decays exponentially with time. Because of this time dependency, insulation resistance is normally calculated and recorded one minute after the test voltage is applied."

    FIST 4-7, section 6.1.28, page 83, August 2023. Agency copy of FIST 4-7

    The current standard governs; this passage is a public-domain description of the practice dated August 2023.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-13created
2026-10-13reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.insulation-resistance.definition." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/data/tests.insulation-resistance.definition/.
Electrical Testing Reference, Data record tests.insulation-resistance.definition (Oct. 13, 2026), https://www.electricaltestingreference.com/data/tests.insulation-resistance.definition/.
@misc{etr-data-tests-insulation-resistance-definition,
  title = {Data record tests.insulation-resistance.definition},
  howpublished = {\url{https://www.electricaltestingreference.com/data/tests.insulation-resistance.definition/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {last substantive change 2026-10-13}
}
{{cite web |title=Data record tests.insulation-resistance.definition |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/data/tests.insulation-resistance.definition/ |date=2026-10-13 |access-date=}}