Data record tests.insulation-resistance.equipment.cable.maintenance

Verified 2026-10-13 Confidence: Medium

Provenance pending: the source of this record has not yet been confirmed as official.

Insulation Resistance is specified for low-voltage cables in maintenance testing at clause 7.3.2.B of ANSI/NETA MTS-2023.

Value: low-voltage cables

ProvenanceANSI/NETA MTS-2023 supports data record tests.insulation-resistance.equipment.cable.maintenance, which is cited on the entry Insulation Resistance.SOURCEANSI/NETA MTS-2023ANSI/NETA MTS-2023Licensed standard, clause 7.3.2.BDATA RECORDtests.insulation-resistance.equipment.cable.maintenancetests.insulation-resista..Verified 2026-10-13ENTRYInsulation ResistanceInsulation Resistance1 revision
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/NETA MTS-2023Licensed standard, clause 7.3.2.B
Data recordtests.insulation-resistance.equipment.cable.maintenanceVerified 2026-10-13
EntryInsulation Resistance1 revision
Subject
Insulation Resistance (Test methods)
Kind
Equipment fact
Source
ANSI/NETA MTS-2023, clause 7.3.2.B, Maintenance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA MTS-2023Publisher information page
Also stated in
  • Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.e, PDF page 82, printed 5-15, item (1) Temperature (29 November 1996).
    Read the reference passage

    5-27.e. Factors affecting insulation resistance

    "Insulation resistance varies with the temperature, and the effect of temperature depends on many other things, such as type of insulation, amount of moisture in and on the surface, and the condition of the surface. All spot-test readings should be corrected to a base temperature such as 40 degrees C."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.e, PDF page 82, printed 5-15, item (1) Temperature, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

  • TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.f, PDF page 82, printed 5-15, the ellipsis drops one sentence on resistance against cable length whose OCR is broken (29 November 1996).
    Read the reference passage

    5-27.f. Interpretations

    "The spot-test reading should be taken after a 60-second voltage application. [...] A gradual decline in resistance with age is normal; however, a sudden decline means insulation failure is imminent and a continued downward trend indicates insulation deterioration, even though measured resistance values are above the minimum acceptable limits."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.f, PDF page 82, printed 5-15, the ellipsis drops one sentence on resistance against cable length whose OCR is broken, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

  • Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27, PDF page 81, printed 5-14 (29 November 1996).
    Read the reference passage

    5-27. Cable insulation resistance tests

    "Insulation resistance is the resistance which the insulation presents to a flow of current, from an impressed direct-current voltage. An insulation resistance test is a short-time test made to indicate the suitability of the insulation for the purpose intended, or to indicate whether an overpotential test can be made without damaging the insulation. It is not a dielectric strength test, but will give an indication of the insulation's condition with respect to moisture and other contamination."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27, PDF page 81, printed 5-14, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-13created
2026-10-13edited

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.insulation-resistance.equipment.cable.maintenance." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/data/tests.insulation-resistance.equipment.cable.maintenance/.
Electrical Testing Reference, Data record tests.insulation-resistance.equipment.cable.maintenance (Oct. 13, 2026), https://www.electricaltestingreference.com/data/tests.insulation-resistance.equipment.cable.maintenance/.
@misc{etr-data-tests-insulation-resistance-equipment-cable-maintenance,
  title = {Data record tests.insulation-resistance.equipment.cable.maintenance},
  howpublished = {\url{https://www.electricaltestingreference.com/data/tests.insulation-resistance.equipment.cable.maintenance/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {last substantive change 2026-10-13}
}
{{cite web |title=Data record tests.insulation-resistance.equipment.cable.maintenance |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/data/tests.insulation-resistance.equipment.cable.maintenance/ |date=2026-10-13 |access-date=}}