Clause 10.11 of IEEE C57.12.90-2021 tests insulation resistance with the windings immersed, short-circuited and fitted with their bushings; circuits at the same voltage above ground are connected together while groups at different voltages are tested one at a time, the direct voltage is raised in increments with a hold at each step while the current is read, the test stops at once if the current keeps rising instead of settling, the direct voltage to ground stays within the low-frequency applied-voltage level of clause 10.6, and every terminal is grounded afterward until the trapped charge has drained.
| Step | Item | Detail |
|---|---|---|
| Source | IEEE C57.12.90-2021 | Licensed standard, clause 10.11.1, 10.11.2, 10.11.3, 10.11.4 |
| Data record | tests.insulation-resistance.ieeec57-12-90.procedure | Verified 2026-10-24 |
| Entry | Insulation Resistance | 1 revision |
- Subject
- Insulation Resistance (Test methods)
- Kind
- Method fact
- Source
- IEEE C57.12.90-2021, clause 10.11.1, 10.11.2, 10.11.3, 10.11.4, Test Code for Liquid-Immersed Distribution, Power and Regulating Transformers, IEEE.
History
| Date | Change |
|---|---|
| 2026-10-24 | created |
| 2026-10-24 | revised |
| 2026-10-24 | review_status unreviewed -> software_reviewed |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record tests.insulation-resistance.ieeec57-12-90.procedure." Electrical Testing Reference. 2026-10-24. https://www.electricaltestingreference.com/data/tests.insulation-resistance.ieeec57-12-90.procedure/.
Electrical Testing Reference, Data record tests.insulation-resistance.ieeec57-12-90.procedure (Oct. 24, 2026), https://www.electricaltestingreference.com/data/tests.insulation-resistance.ieeec57-12-90.procedure/.
@misc{etr-data-tests-insulation-resistance-ieeec57-12-90-procedure,
title = {Data record tests.insulation-resistance.ieeec57-12-90.procedure},
howpublished = {\url{https://www.electricaltestingreference.com/data/tests.insulation-resistance.ieeec57-12-90.procedure/}},
organization = {Electrical Testing Reference},
publisher = {Electrical Testing Reference},
year = {2026},
note = {last substantive change 2026-10-24}
}{{cite web |title=Data record tests.insulation-resistance.ieeec57-12-90.procedure |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/data/tests.insulation-resistance.ieeec57-12-90.procedure/ |date=2026-10-24 |access-date=}}