Data record tests.insulation-resistance.trending-conditions
Verified 2026-10-13 Confidence: High
IEEE 43-2013 compares readings over time only when the tests were made at similar winding temperature, test voltage, duration and humidity, with the readings brought to a common temperature.
| Step | Item | Detail |
|---|---|---|
| Source | IEEE 43-2013 | Licensed standard, clause 11.1 |
| Data record | tests.insulation-resistance.trending-conditions | Verified 2026-10-13 |
| Entry | Insulation Resistance | 1 revision |
- Subject
- Insulation Resistance (Test methods)
- Kind
- Method fact
- Source
- IEEE 43-2013, clause 11.1, Recommended Practice for Testing Insulation Resistance of Electric Machinery, IEEE. Publisher page for IEEE 43-2013Publisher information page
- Also stated in
- TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.f, PDF page 82, printed 5-15, the ellipsis drops one sentence on resistance against cable length whose OCR is broken (29 November 1996).
Read the reference passage
5-27.f. Interpretations
"The spot-test reading should be taken after a 60-second voltage application. [...] A gradual decline in resistance with age is normal; however, a sudden decline means insulation failure is imminent and a continued downward trend indicates insulation deterioration, even though measured resistance values are above the minimum acceptable limits."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.f, PDF page 82, printed 5-15, the ellipsis drops one sentence on resistance against cable length whose OCR is broken, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-31, PDF page 84, printed 5-17, the ellipsis drops one sentence on scheduling tests with maintenance outages (29 November 1996).
Read the reference passage
5-31. Cable test records
"It is very important that cable records be made for any inspection or test on any circuit. Such records should flag when the next inspection or maintenance outage is to be made. [...] The trend of the reading obtained will determine whether the cable is stable, slightly aging, or rapidly deteriorating. Slight decreases in the insulation resistance each year are to be expected as the cable ages. Tests should be made more frequently if more than the usual decrease indicates that deterioration is approaching a critical state."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-31, PDF page 84, printed 5-17, the ellipsis drops one sentence on scheduling tests with maintenance outages, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.f, PDF page 82, printed 5-15, the ellipsis drops one sentence on resistance against cable length whose OCR is broken (29 November 1996).
History
| Date | Change |
|---|---|
| 2026-10-13 | created |
| 2026-10-13 | reviewed |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record tests.insulation-resistance.trending-conditions." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/data/tests.insulation-resistance.trending-conditions/.
Electrical Testing Reference, Data record tests.insulation-resistance.trending-conditions (Oct. 13, 2026), https://www.electricaltestingreference.com/data/tests.insulation-resistance.trending-conditions/.
@misc{etr-data-tests-insulation-resistance-trending-conditions,
title = {Data record tests.insulation-resistance.trending-conditions},
howpublished = {\url{https://www.electricaltestingreference.com/data/tests.insulation-resistance.trending-conditions/}},
organization = {Electrical Testing Reference},
publisher = {Electrical Testing Reference},
year = {2026},
note = {last substantive change 2026-10-13}
}{{cite web |title=Data record tests.insulation-resistance.trending-conditions |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/data/tests.insulation-resistance.trending-conditions/ |date=2026-10-13 |access-date=}}