IEEE 43-2013 compares readings over time only when the tests were made at similar winding temperature, test voltage, duration and humidity, with the readings brought to a common temperature.

ProvenanceIEEE 43-2013 supports data record tests.insulation-resistance.trending-conditions, which is cited on the entry Insulation Resistance.SOURCEIEEE 43-2013IEEE 43-2013Licensed standard, clause 11.1DATA RECORDtests.insulation-resistance.trending-conditionstests.insulation-resista..Verified 2026-10-13ENTRYInsulation ResistanceInsulation Resistance1 revision
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceIEEE 43-2013Licensed standard, clause 11.1
Data recordtests.insulation-resistance.trending-conditionsVerified 2026-10-13
EntryInsulation Resistance1 revision
Subject
Insulation Resistance (Test methods)
Kind
Method fact
Source
IEEE 43-2013, clause 11.1, Recommended Practice for Testing Insulation Resistance of Electric Machinery, IEEE. Publisher page for IEEE 43-2013Publisher information page
Also stated in
  • TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.f, PDF page 82, printed 5-15, the ellipsis drops one sentence on resistance against cable length whose OCR is broken (29 November 1996).
    Read the reference passage

    5-27.f. Interpretations

    "The spot-test reading should be taken after a 60-second voltage application. [...] A gradual decline in resistance with age is normal; however, a sudden decline means insulation failure is imminent and a continued downward trend indicates insulation deterioration, even though measured resistance values are above the minimum acceptable limits."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.f, PDF page 82, printed 5-15, the ellipsis drops one sentence on resistance against cable length whose OCR is broken, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

  • TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-31, PDF page 84, printed 5-17, the ellipsis drops one sentence on scheduling tests with maintenance outages (29 November 1996).
    Read the reference passage

    5-31. Cable test records

    "It is very important that cable records be made for any inspection or test on any circuit. Such records should flag when the next inspection or maintenance outage is to be made. [...] The trend of the reading obtained will determine whether the cable is stable, slightly aging, or rapidly deteriorating. Slight decreases in the insulation resistance each year are to be expected as the cable ages. Tests should be made more frequently if more than the usual decrease indicates that deterioration is approaching a critical state."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-31, PDF page 84, printed 5-17, the ellipsis drops one sentence on scheduling tests with maintenance outages, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-13created
2026-10-13reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.insulation-resistance.trending-conditions." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/data/tests.insulation-resistance.trending-conditions/.
Electrical Testing Reference, Data record tests.insulation-resistance.trending-conditions (Oct. 13, 2026), https://www.electricaltestingreference.com/data/tests.insulation-resistance.trending-conditions/.
@misc{etr-data-tests-insulation-resistance-trending-conditions,
  title = {Data record tests.insulation-resistance.trending-conditions},
  howpublished = {\url{https://www.electricaltestingreference.com/data/tests.insulation-resistance.trending-conditions/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {last substantive change 2026-10-13}
}
{{cite web |title=Data record tests.insulation-resistance.trending-conditions |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/data/tests.insulation-resistance.trending-conditions/ |date=2026-10-13 |access-date=}}