SF6 Gas Quality
Updated 2026-10-13
| Relationship | Entry |
|---|---|
| Governing standard | ANSI/NETA ATS-2025 (ANSI/NETA ATS-2025 Standard for Acceptance Testing Specifications) |
| Governing standard | ANSI/NETA MTS-2023 (ANSI/NETA MTS-2023 Standard for Maintenance Testing Specifications) |
Data records
- SF6 Gas Quality is addressed in ANSI/NETA ATS-2025.
- SF6 Gas Quality is addressed in ANSI/NETA MTS-2023.
- The test method is named SF6 Gas Quality. Value: SF6 Gas Quality.
Elsewhere in the family
- SF6 Gas Quality more on this entry on Circuit Breaker Reference
- SF6 Gas Quality more on this entry on Switchgear Testing Reference
- Dissolved Gas Analysis related entry on Insulating Fluid Reference
- Gas Blanket Oxygen Content related entry on Transformer Testing Reference
- Insulating Liquid Acid Number related entry on Insulating Fluid Reference
- Insulating Liquid Color related entry on Insulating Fluid Reference
- Insulating Liquid Dielectric Breakdown related entry on Insulating Fluid Reference
- Insulating Liquid Interfacial Tension related entry on Insulating Fluid Reference
- SF6 gas analyzer related entry on Test Instrument Reference
Sources
- ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 7.5.4.B.4. Held as: Purchased single-user copy. Publisher page for ANSI/NETA ATS-2025Publisher information page
- ANSI/NETA MTS-2023, Maintenance Testing Specifications for Electrical Power Equipment and Systems, 2023 edition, NETA. Cited: clause 7.5.4.B. Held as: Purchased single-user copy. Publisher page for ANSI/NETA MTS-2023Publisher information page
- Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
Also stated in
- FIST 4-7, section 6.1.53.1, page 144 (August 2023).
Read the reference passage
6.1.53.1 Gas Pressure Test
"SF6 gas should be tested for purity, water content, and arcing biproducts prior to energization using a calibrated SF6 gas analyzer to ensure the gas will perform properly when interrupting faults or loads. [...] If in doubt about the gas analyzer results, do not put the gas into service and seek advice from an SF6 expert or certified SF6 gas handler. Gas that does not meet minimum standards should be properly recycled."
FIST 4-7, section 6.1.53.1, page 144, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
- FIST 3-16, section 8.2.6, page 66 (May 2024).
Read the reference passage
8.2.6 Insulation Resistance Test
"The insulation resistance test is a test that is replaced by the SF6 gas analysis. Since the SF6 gas is the insulation of the breaker, the gas analysis will provide a good indication to the quality of the insulating condition of the gas."
FIST 3-16, section 8.2.6, page 66, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 3-16, section 8.3.1, page 67 (May 2024).
Read the reference passage
8.3.1 SF6 Gas Analysis
"An SF6 gas analysis is extremely important to determine the condition of your breaker. Similar to the Dissolved Gas Analysis (DGA) for oil used for transformers and oil circuit breakers, this test can uncover possible problems with the breaker seals and gaskets. It may also help determine other problems that may be occurring inside the breaker."
FIST 3-16, section 8.3.1, page 67, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 3-16, section 8.3.1, page 68 (May 2024).
Read the reference passage
8.3.1 SF6 Gas Analysis
"Moisture within SF6 gas can be the most critical contaminant within the breaker. When SF6 gas and moisture are heated it will create many hazardous and destructive contaminants, the most common being SO2. SO2 is an acid which can affect the insulating surfaces of the breaker and the insulative quality of the gas."
FIST 3-16, section 8.3.1, page 68, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 3-16, section 8.3.1, page 68 (May 2024).
Read the reference passage
8.3.1 SF6 Gas Analysis
"Purity of SF6 gas is the amount of air mixed with the gas. The usual cause of low purity in SF6 gas is not following proper procedures for installing gas into the breaker. It can also be caused by faulty gas carts or filtering equipment."
FIST 3-16, section 8.3.1, page 68, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 3-16, section 8.4, page 75 (May 2024).
Read the reference passage
8.4 Condition Based Maintenance
"If the amount of contaminants within the breaker continue to be a problem or the breaker is leaking gas, it is a good sign that the seals need to be replaced."
FIST 3-16, section 8.4, page 75, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 3-16, section 9.5.1, page 80 (May 2024).
Read the reference passage
9.5.1 SF6 Gas Testing
"The SF6 gas analysis may be performed using an SF6 gas analyzer, or by using a lab which will require a sample of the gas be pulled and sent to the lab. Prior to drawing gas, make sure all hoses and connector surfaces are clean and dry. It is best to draw SF6 gas on a warm dry day. Moisture within the breaker can condense or freeze and give an inaccurate moisture reading. The ambient temperature when the sample was taken should always be recorded."
FIST 3-16, section 9.5.1, page 80, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
Obtaining the documents
- ANSI/NETA ATS-2025: available from the publisher
- ANSI/NETA MTS-2023: available from the publisher
Changelog (3 entries)
| Date | Revision | Change |
|---|---|---|
| 2026-10-13 | created (tests.sf6-gas-quality.governed-by.ansi-neta-ats) | |
| 2026-10-13 | created (tests.sf6-gas-quality.governed-by.ansi-neta-mts) | |
| 2026-10-13 | created (tests.sf6-gas-quality.title) |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"SF6 Gas Quality." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/tests/sf6-gas-quality/.
Electrical Testing Reference, SF6 Gas Quality (Oct. 13, 2026), https://www.electricaltestingreference.com/tests/sf6-gas-quality/.
@misc{etr-tests-sf6-gas-quality,
title = {SF6 Gas Quality},
howpublished = {\url{https://www.electricaltestingreference.com/tests/sf6-gas-quality/}},
organization = {Electrical Testing Reference},
publisher = {Electrical Testing Reference},
year = {2026},
note = {last substantive change 2026-10-13}
}{{cite web |title=SF6 Gas Quality |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/tests/sf6-gas-quality/ |date=2026-10-13 |access-date=}}