Data record gloss.polarization-index.definition

Verified 2026-10-13 Confidence: High

The polarization index is the ratio of two insulation resistance readings taken at two times after a direct voltage is applied, the later reading divided by the earlier one.

ProvenanceElectrical Testing Reference editorial taxonomy supports data record gloss.polarization-index.definition, which is cited on the entry Polarization index.SOURCEElectrical Testing Reference editorial taxonomyElectrical Testing Refer..Own observationDATA RECORDgloss.polarization-index.definitiongloss.polarization-index..Verified 2026-10-13ENTRYPolarization indexPolarization index1 revision
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceElectrical Testing Reference editorial taxonomyOwn observation
Data recordgloss.polarization-index.definitionVerified 2026-10-13
EntryPolarization index1 revision
Subject
Polarization index (Glossary)
Kind
Definition
Source
Electrical Testing Reference editorial taxonomy, 2026-10 edition, Electrical Testing Reference editorial taxonomy of test methods, Electrical Testing Reference.
Also stated in
  • FIST 4-7, section 6.1.28, page 84 (August 2023).
    Read the reference passage

    6.1.28 Generator and Large Motor Windings

    "A polarization index test is similar to the insulation resistance test except that current (or resistance) readings are taken at two intervals, normally one and ten minutes after application of the voltage step. [...] A stator winding may fail the PI test if it has absorbed significant moisture, has substantial surface contamination, or major physical damage. Prior to performing ac or dc high-potential acceptance testing, the winding must pass the PI test."

    FIST 4-7, section 6.1.28, page 84, August 2023. Agency copy of FIST 4-7

    The current standard governs; this passage is a public-domain description of the practice dated August 2023.

  • FIST 4-7, section 6.1.8.1, page 38 (August 2023).
    Read the reference passage

    6.1.8.1 Insulation Resistance and Polarization Index (PI) Testing

    "To perform a test, a specified high, direct voltage is applied to the test specimen and held for 10 minutes. At the 1- and 10-minute intervals, the insulation resistance and/or current are recorded. The insulation resistance is the value recorded at the 1-minute interval. Often the value will be corrected to a normalized temperature of 40 °C."

    FIST 4-7, section 6.1.8.1, page 38, August 2023. Agency copy of FIST 4-7

    The current standard governs; this passage is a public-domain description of the practice dated August 2023.

  • Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.g, PDF page 82, printed 5-15, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "deterioration the need" is printed so (29 November 1996).
    Read the reference passage

    5-27.g. Dielectric absorption test

    "This test is usually conducted at higher voltages for extended periods of from 5 to 15 minutes. Since the current is inversely related to time, insulation resistance will rise gradually for a good cable but will flatten rapidly otherwise. Periodic readings should be taken and plotted against time. [...] A polarization index of two or higher indicates good insulation, while a polarization index of less than one indicates cable deterioration the need for immediate maintenance."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.g, PDF page 82, printed 5-15, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "deterioration the need" is printed so, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

  • Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 7-7.b, PDF page 99, printed 7-7, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "of a 2" is printed so (29 November 1996).
    Read the reference passage

    7-7.b. Polarization index (PI) test

    "A PI test or dielectric absorption test is a continuation of the insulation resistance test in which the voltage is applied for a longer period of time. For good insulation, the resistance values will increase with time. [...] An index below 1 indicates poor insulation. An index between 1 and 2 indicates that the insulation is questionable. An index of a 2 and higher indicates good insulation."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 7-7.b, PDF page 99, printed 7-7, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "of a 2" is printed so, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-13created
2026-10-13reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record gloss.polarization-index.definition." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/data/gloss.polarization-index.definition/.
Electrical Testing Reference, Data record gloss.polarization-index.definition (Oct. 13, 2026), https://www.electricaltestingreference.com/data/gloss.polarization-index.definition/.
@misc{etr-data-gloss-polarization-index-definition,
  title = {Data record gloss.polarization-index.definition},
  howpublished = {\url{https://www.electricaltestingreference.com/data/gloss.polarization-index.definition/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {last substantive change 2026-10-13}
}
{{cite web |title=Data record gloss.polarization-index.definition |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/data/gloss.polarization-index.definition/ |date=2026-10-13 |access-date=}}