Polarization index
Updated 2026-10-13
The polarization index is the ratio of two insulation resistance readings taken during one application of direct voltage, the later reading divided by the earlier. [1] In IEEE 43-2013 the two readings are taken 10 min and 1 min after the voltage is applied. [2] [3] [4]
Usage
The term appears in IEEE 43-2013, which covers the windings of rotating machines, and in ANSI/NETA ATS-2025 and ANSI/NETA MTS-2023. [Motor Testing Reference] [5] [6] As a ratio of two resistances the index is dimensionless and is stated without a unit. [7]
See also
Related entries include insulation resistance, the quantity from which the index is formed, and the dielectric absorption ratio, a variant based on shorter reading times. [8] [9]
Notes
- Electrical Testing Reference editorial taxonomy, 2026-10 edition. The polarization index is the ratio of two insulation resistance readings taken at two times after a direct voltage is applied, the later reading divided by the earlier one. Datum gloss.polarization-index.definition
- IEEE 43-2013, clause 5.4. IEEE 43-2013 defines the polarization index as the insulation resistance read after ten minutes of applied voltage divided by the insulation resistance read after one minute. Datum tests.polarization-index-and-dielectric-absorption.pi-definition
- IEEE 43-2013, clause 5.4. The later of the two readings that make up the polarization index under IEEE 43-2013 is taken ten minutes after the test voltage is applied. Value: 10 min. Datum tests.polarization-index-and-dielectric-absorption.ten-minute
- IEEE 43-2013, clause 5.3. Under IEEE 43-2013 the reference insulation resistance reading is the one taken when the test voltage has been applied for one minute. Value: 1 min. Datum tests.insulation-resistance.one-minute-reading
- ANSI/NETA ATS-2025, clause 7.20.3.2.B.2. Polarization Index and Dielectric Absorption is addressed in ANSI/NETA ATS-2025. Datum tests.polarization-index-and-dielectric-absorption.governed-by.ansi-neta-ats(provenance pending)
- ANSI/NETA MTS-2023, clause 7.20.3.2.B. Polarization Index and Dielectric Absorption is addressed in ANSI/NETA MTS-2023. Datum tests.polarization-index-and-dielectric-absorption.governed-by.ansi-neta-mts(provenance pending)
- NIST SP 811, web page updated 2025-08-18 edition, clause Table 3, note b. The NIST Guide to the SI notes that the symbol for the derived unit one is generally omitted when values of dimensionless quantities are stated. Datum qty.dissipation-factor.unit-one
- Electrical Testing Reference editorial taxonomy, 2026-10 edition. The dielectric absorption ratio is the ratio of two insulation resistance readings taken a short time apart early in a direct-voltage test, the later reading divided by the earlier one. Datum gloss.dielectric-absorption-ratio.definition
- IEEE 43-2013, clause Annex A. Annex A of IEEE 43-2013 describes variants of the polarization index built on shorter reading times and states that no agreed pass or fail criteria exist for them. Datum tests.polarization-index-and-dielectric-absorption.annex-variants
Data records
- The polarization index is the ratio of two insulation resistance readings taken at two times after a direct voltage is applied, the later reading divided by the earlier one.
Elsewhere in the family
- Polarization index more on this entry on Test Instrument Reference
- Guard terminal related entry on Test Instrument Reference
- Step voltage test related entry on Test Instrument Reference
- Absorption current related entry on Test Instrument Reference
- Dielectric frequency response related entry on Test Instrument Reference
- Insulation resistance tester related entry on Test Instrument Reference
- DC hipot test set related entry on Test Instrument Reference
- Dielectric frequency response analyzer related entry on Test Instrument Reference
- Motor circuit analyzer related entry on Test Instrument Reference
- Surge tester related entry on Test Instrument Reference
Sources
- ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 7.20.3.2.B.2. Held as: Purchased single-user copy. Publisher page for ANSI/NETA ATS-2025Publisher information page
- ANSI/NETA MTS-2023, Maintenance Testing Specifications for Electrical Power Equipment and Systems, 2023 edition, NETA. Cited: clause 7.20.3.2.B. Held as: Purchased single-user copy. Publisher page for ANSI/NETA MTS-2023Publisher information page
- Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
- IEEE 43-2013, Recommended Practice for Testing Insulation Resistance of Electric Machinery, 2013 edition, IEEE. Cited: clause 5.4; clause 5.3; clause Annex A. Held as: Purchased single-user copy. Publisher page for IEEE 43-2013Publisher information page
- NIST SP 811, NIST Guide to the SI, Chapter 4: The Two Classes of SI Units and the SI Prefixes, web page updated 2025-08-18 edition, NIST. Cited: clause Table 3, note b. Agency document. Held as: Government work. Agency copy of NIST SP 811
Also stated in
- FIST 4-7, section 6.1.28, page 84 (August 2023).
Read the reference passage
6.1.28 Generator and Large Motor Windings
"A polarization index test is similar to the insulation resistance test except that current (or resistance) readings are taken at two intervals, normally one and ten minutes after application of the voltage step. [...] A stator winding may fail the PI test if it has absorbed significant moisture, has substantial surface contamination, or major physical damage. Prior to performing ac or dc high-potential acceptance testing, the winding must pass the PI test."
FIST 4-7, section 6.1.28, page 84, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
- FIST 4-7, section 6.1.8.1, page 38 (August 2023).
Read the reference passage
6.1.8.1 Insulation Resistance and Polarization Index (PI) Testing
"To perform a test, a specified high, direct voltage is applied to the test specimen and held for 10 minutes. At the 1- and 10-minute intervals, the insulation resistance and/or current are recorded. The insulation resistance is the value recorded at the 1-minute interval. Often the value will be corrected to a normalized temperature of 40 °C."
FIST 4-7, section 6.1.8.1, page 38, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
- Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.g, PDF page 82, printed 5-15, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "deterioration the need" is printed so (29 November 1996).
Read the reference passage
5-27.g. Dielectric absorption test
"This test is usually conducted at higher voltages for extended periods of from 5 to 15 minutes. Since the current is inversely related to time, insulation resistance will rise gradually for a good cable but will flatten rapidly otherwise. Periodic readings should be taken and plotted against time. [...] A polarization index of two or higher indicates good insulation, while a polarization index of less than one indicates cable deterioration the need for immediate maintenance."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.g, PDF page 82, printed 5-15, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "deterioration the need" is printed so, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 7-7.b, PDF page 99, printed 7-7, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "of a 2" is printed so (29 November 1996).
Read the reference passage
7-7.b. Polarization index (PI) test
"A PI test or dielectric absorption test is a continuation of the insulation resistance test in which the voltage is applied for a longer period of time. For good insulation, the resistance values will increase with time. [...] An index below 1 indicates poor insulation. An index between 1 and 2 indicates that the insulation is questionable. An index of a 2 and higher indicates good insulation."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 7-7.b, PDF page 99, printed 7-7, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "of a 2" is printed so, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- FIST 4-7, section 6.1.8.1, page 37 (August 2023).
Read the reference passage
6.1.8.1 Insulation Resistance and Polarization Index (PI) Testing
"Insulation resistance and PI testing applies a high, direct-voltage to the test specimen and measures the corresponding current through the insulation system of interest. These tests must be successfully completed prior to performing a high-potential withstand (proof) test, also known as a 'hipot' test. If the test specimen yields poor insulation resistance or unacceptable polarization index results, the problem must be identified and corrected, and the specimen must pass a repeat testing prior to performing final high-potential withstand test."
FIST 4-7, section 6.1.8.1, page 37, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
- FIST 4-7, section 6.1.28, page 86 (August 2023).
Read the reference passage
6.1.28 Generator and Large Motor Windings
"Field windings often do not achieve the same polarization index values as stator windings because they utilize different insulation components, often with lower polarizability. Thus, the same metrics applied to stator windings may not always apply to field winding insulation systems."
FIST 4-7, section 6.1.28, page 86, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
Obtaining the documents
- ANSI/NETA ATS-2025: available from the publisher
- ANSI/NETA MTS-2023: available from the publisher
- IEEE 43-2013: available from the publisher
Changelog (17 entries)
| Date | Revision | Change |
|---|---|---|
| 2026-10-13 | created (gloss.dielectric-absorption-ratio.definition) | |
| 2026-10-13 | reviewed (gloss.dielectric-absorption-ratio.definition) | |
| 2026-10-13 | created (gloss.polarization-index.definition) | |
| 2026-10-13 | reviewed (gloss.polarization-index.definition) | |
| 2026-10-13 | 1 | created |
| 2026-10-13 | created (qty.dissipation-factor.unit-one) | |
| 2026-10-13 | reviewed (qty.dissipation-factor.unit-one) | |
| 2026-10-13 | created (tests.insulation-resistance.one-minute-reading) | |
| 2026-10-13 | reviewed (tests.insulation-resistance.one-minute-reading) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.annex-variants) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.annex-variants) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.governed-by.ansi-neta-ats) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.governed-by.ansi-neta-mts) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.pi-definition) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.pi-definition) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.ten-minute) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.ten-minute) |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
Permanent revision URL: https://www.electricaltestingreference.com/glossary/polarization-index/rev/1/. Current version: https://www.electricaltestingreference.com/glossary/polarization-index/.
"Polarization index." Electrical Testing Reference. Revision 1, 2026-10-13. https://www.electricaltestingreference.com/glossary/polarization-index/rev/1/.
Electrical Testing Reference, Polarization index (rev. 1, Oct. 13, 2026), https://www.electricaltestingreference.com/glossary/polarization-index/rev/1/.
@misc{etr-glossary-polarization-index-rev1,
title = {Polarization index},
howpublished = {\url{https://www.electricaltestingreference.com/glossary/polarization-index/rev/1/}},
organization = {Electrical Testing Reference},
publisher = {Electrical Testing Reference},
year = {2026},
note = {Revision 1; last substantive change 2026-10-13}
}{{cite web |title=Polarization index |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/glossary/polarization-index/rev/1/ |date=2026-10-13 |access-date= |version=1}}