Data record tests.dielectric-withstand.ieeec57-12-90.induced-voltage

Verified 2026-10-24 Confidence: Medium

Clauses 10.7 and 10.8 of IEEE C57.12.90-2021 perform the induced-voltage test by exciting the transformer at a raised frequency so that the core does not saturate, for a duration stated in cycles or time, with the Class II procedure adding an enhancement level followed by a lower level held for an extended period during which partial discharge is read at intervals and judged against the magnitude, rise and trend criteria of clause 10.8.5.

ProvenanceIEEE C57.12.90-2021 supports data record tests.dielectric-withstand.ieeec57-12-90.induced-voltage, which is cited on the entry Dielectric Withstand.SOURCEIEEE C57.12.90-2021IEEE C57.12.90-2021Licensed standard, clause 10.7, 10.8DATA RECORDtests.dielectric-withstand.ieeec57-12-90.induced-voltagetests.dielectric-withsta..Verified 2026-10-24ENTRYDielectric WithstandDielectric WithstandNo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceIEEE C57.12.90-2021Licensed standard, clause 10.7, 10.8
Data recordtests.dielectric-withstand.ieeec57-12-90.induced-voltageVerified 2026-10-24
EntryDielectric WithstandNo revisions
Subject
Dielectric Withstand (Test methods)
Kind
Method fact
Source
IEEE C57.12.90-2021, clause 10.7, 10.8, Test Code for Liquid-Immersed Distribution, Power and Regulating Transformers, IEEE.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-24created
2026-10-24revised
2026-10-24review_status unreviewed -> software_reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.dielectric-withstand.ieeec57-12-90.induced-voltage." Electrical Testing Reference. 2026-10-24. https://www.electricaltestingreference.com/data/tests.dielectric-withstand.ieeec57-12-90.induced-voltage/.