Data record tests.infrared-thermographic-survey.governed-by.ansi-neta-ats

Verified 2026-10-13 Confidence: Medium

Provenance pending: the source of this record has not yet been confirmed as official.

Infrared Thermographic Survey is addressed in ANSI/NETA ATS-2025.

ProvenanceANSI/NETA ATS-2025 supports data record tests.infrared-thermographic-survey.governed-by.ansi-neta-ats, which is cited on the entry Infrared Thermographic Survey.SOURCEANSI/NETA ATS-2025ANSI/NETA ATS-2025Licensed standard, clause 9DATA RECORDtests.infrared-thermographic-survey.governed-by.ansi-neta-atstests.infrared-thermogra..Verified 2026-10-13ENTRYInfrared Thermographic SurveyInfrared Thermographic S..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/NETA ATS-2025Licensed standard, clause 9
Data recordtests.infrared-thermographic-survey.governed-by.ansi-neta-atsVerified 2026-10-13
EntryInfrared Thermographic SurveyNo revisions
Subject
Infrared Thermographic Survey (Test methods)
Kind
Method fact
Source
ANSI/NETA ATS-2025, clause 9, Acceptance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA ATS-2025Publisher information page
Also stated in
  • FIST 3-16, section 3.3.2, pages 24 to 25 (May 2024).
    Read the reference passage

    3.3.2 Infrared Scan and Thermal Analysis

    "An infrared scan is perhaps the most useful MCCB maintenance tool. It can quickly reveal loose connections, high internal resistance of individual contacts, and overloaded conductors. It is very important to note that the actual temperature within the breaker may be up to four times hotter than what is displayed on the outer case. So, it is very important that a hot spot found on an IR scan be investigated. It is also important that trending of the IR scans is performed."

    FIST 3-16, section 3.3.2, pages 24 to 25, May 2024. Agency copy of FIST 3-16

    The current standard governs; this passage is a public-domain description of the practice dated May 2024.

  • FIST 3-16, section 3.3.2, page 25 (May 2024).
    Read the reference passage

    3.3.2 Infrared Scan and Thermal Analysis

    "While performing IR scans of MCCBs, they must be carrying normal load current or the scan must be done immediately after de-energizing. Due to rapid temperature decrease, an IR scan is useless if the circuit has been de-energized more than a few seconds prior to the scan."

    FIST 3-16, section 3.3.2, page 25, May 2024. Agency copy of FIST 3-16

    The current standard governs; this passage is a public-domain description of the practice dated May 2024.

  • FIST 3-16, section 4.2.8, page 33 (May 2024).
    Read the reference passage

    4.2.8 Infrared Scan and Thermal Analysis

    "Infrared scan or thermal scan/analysis allows for nonintrusive analysis of temperature and thermal characteristics or thermal patterns of circuit breaker and its components. Infrared scan may dynamically detect abnormal thermal conditions or changes in temperature that may indicate problems in circuit breakers in their incipient stages. Different technologies are available in the industry to detect dynamic changes in heating; however, using thermal imaging cameras is preferred."

    FIST 3-16, section 4.2.8, page 33, May 2024. Agency copy of FIST 3-16

    The current standard governs; this passage is a public-domain description of the practice dated May 2024.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-13created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.infrared-thermographic-survey.governed-by.ansi-neta-ats." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/data/tests.infrared-thermographic-survey.governed-by.ansi-neta-ats/.
Electrical Testing Reference, Data record tests.infrared-thermographic-survey.governed-by.ansi-neta-ats (Oct. 13, 2026), https://www.electricaltestingreference.com/data/tests.infrared-thermographic-survey.governed-by.ansi-neta-ats/.
@misc{etr-data-tests-infrared-thermographic-survey-governed-by-ansi-neta-ats,
  title = {Data record tests.infrared-thermographic-survey.governed-by.ansi-neta-ats},
  howpublished = {\url{https://www.electricaltestingreference.com/data/tests.infrared-thermographic-survey.governed-by.ansi-neta-ats/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {last substantive change 2026-10-13}
}
{{cite web |title=Data record tests.infrared-thermographic-survey.governed-by.ansi-neta-ats |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/data/tests.infrared-thermographic-survey.governed-by.ansi-neta-ats/ |date=2026-10-13 |access-date=}}