Infrared Thermographic Survey
Updated 2026-10-13
| Relationship | Entry |
|---|---|
| Governing standard | ANSI/NETA ATS-2025 (ANSI/NETA ATS-2025 Standard for Acceptance Testing Specifications) |
| Governing standard | ANSI/NETA ECS-2024 (ANSI/NETA ECS-2024 Standard for Electrical Commissioning Specifications) |
Data records
- Infrared Thermographic Survey is specified for equipment surveyed by infrared thermography in acceptance testing at clause 9 of ANSI/NETA ATS-2025. Value: equipment surveyed by infrared thermography.
- Infrared Thermographic Survey is specified for equipment surveyed by infrared thermography in commissioning testing at clause 9 of ANSI/NETA ECS-2024. Value: equipment surveyed by infrared thermography.
- Infrared Thermographic Survey is addressed in ANSI/NETA ATS-2025.
- Infrared Thermographic Survey is addressed in ANSI/NETA ECS-2024.
- The test method is named Infrared Thermographic Survey. Value: Infrared Thermographic Survey.
Elsewhere in the family
- Infrared camera related entry on Test Instrument Reference
Sources
- ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 9. Held as: Purchased single-user copy. Publisher page for ANSI/NETA ATS-2025Publisher information page
- ANSI/NETA ECS-2024, Standard for Electrical Commissioning Specifications, 2024 edition, NETA. Cited: clause 9. Held as: Purchased single-user copy. Publisher page for ANSI/NETA ECS-2024Publisher information page
- Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
Also stated in
- TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 1-16.d, PDF page 16, printed 1-4 (29 November 1996).
Read the reference passage
1-16.d. Testing
"Accessible connections may be tested using an infrared detector only if the connection is under load as covered in chapter 3, section I."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 1-16.d, PDF page 16, printed 1-4, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 3-7.a, PDF page 19, printed 3-1, the ellipsis drops one sentence on instrument sensitivity (29 November 1996).
Read the reference passage
3-7.a. Method
"An infrared detecting device can be used to determine loose connections, overloading of conductors, localized overheating in equipment, or similar conditions before they become serious. [...] Infrared inspection can be done from a distance, since contact with the item being measured is not required. Substation equipment, such as bare bus, disconnect switches, and connections, can be checked without being de-energized."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 3-7.a, PDF page 19, printed 3-1, the ellipsis drops one sentence on instrument sensitivity, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 3-7.c, PDF page 20, printed 3-2, the numbered items (1) to (3) that follow restate NETA MTS values and are not excerpted (29 November 1996).
Read the reference passage
3-7.c. Surveys
"When infrared (thermographic) surveys are made, the equipment to be scanned must be identified. Scanning should be made after visual and mechanical conditions have been observed. Report all areas scanned."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 3-7.c, PDF page 20, printed 3-2, the numbered items (1) to (3) that follow restate NETA MTS values and are not excerpted, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- FIST 3-16, section 3.3.2, pages 24 to 25 (May 2024).
Read the reference passage
3.3.2 Infrared Scan and Thermal Analysis
"An infrared scan is perhaps the most useful MCCB maintenance tool. It can quickly reveal loose connections, high internal resistance of individual contacts, and overloaded conductors. It is very important to note that the actual temperature within the breaker may be up to four times hotter than what is displayed on the outer case. So, it is very important that a hot spot found on an IR scan be investigated. It is also important that trending of the IR scans is performed."
FIST 3-16, section 3.3.2, pages 24 to 25, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 3-16, section 3.3.2, page 25 (May 2024).
Read the reference passage
3.3.2 Infrared Scan and Thermal Analysis
"While performing IR scans of MCCBs, they must be carrying normal load current or the scan must be done immediately after de-energizing. Due to rapid temperature decrease, an IR scan is useless if the circuit has been de-energized more than a few seconds prior to the scan."
FIST 3-16, section 3.3.2, page 25, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 3-16, section 4.2.8, page 33 (May 2024).
Read the reference passage
4.2.8 Infrared Scan and Thermal Analysis
"Infrared scan or thermal scan/analysis allows for nonintrusive analysis of temperature and thermal characteristics or thermal patterns of circuit breaker and its components. Infrared scan may dynamically detect abnormal thermal conditions or changes in temperature that may indicate problems in circuit breakers in their incipient stages. Different technologies are available in the industry to detect dynamic changes in heating; however, using thermal imaging cameras is preferred."
FIST 3-16, section 4.2.8, page 33, May 2024. Agency copy of FIST 3-16
The current standard governs; this passage is a public-domain description of the practice dated May 2024.
- FIST 4-7, section 8.4.12, page 231 (August 2023).
Read the reference passage
8.4.12 Power Transformers
"During incremental loading, use an infrared (IR) scanner to check for hot spots on the tank, bushings, and cooling systems as well as monitor for excessive audible noise and vibration."
FIST 4-7, section 8.4.12, page 231, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
Obtaining the documents
- ANSI/NETA ATS-2025: available from the publisher
- ANSI/NETA ECS-2024: available from the publisher
Changelog (5 entries)
| Date | Revision | Change |
|---|---|---|
| 2026-10-13 | created (tests.infrared-thermographic-survey.equipment.thermographic.acceptance) | |
| 2026-10-13 | created (tests.infrared-thermographic-survey.equipment.thermographic.commissioning) | |
| 2026-10-13 | created (tests.infrared-thermographic-survey.governed-by.ansi-neta-ats) | |
| 2026-10-13 | created (tests.infrared-thermographic-survey.governed-by.ansi-neta-ecs) | |
| 2026-10-13 | created (tests.infrared-thermographic-survey.title) |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Infrared Thermographic Survey." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/tests/infrared-thermographic-survey/.
Electrical Testing Reference, Infrared Thermographic Survey (Oct. 13, 2026), https://www.electricaltestingreference.com/tests/infrared-thermographic-survey/.
@misc{etr-tests-infrared-thermographic-survey,
title = {Infrared Thermographic Survey},
howpublished = {\url{https://www.electricaltestingreference.com/tests/infrared-thermographic-survey/}},
organization = {Electrical Testing Reference},
publisher = {Electrical Testing Reference},
year = {2026},
note = {last substantive change 2026-10-13}
}{{cite web |title=Infrared Thermographic Survey |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/tests/infrared-thermographic-survey/ |date=2026-10-13 |access-date=}}