Data record tests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-ats

Verified 2026-10-13 Confidence: Medium

Provenance pending: the source of this record has not yet been confirmed as official.

Insulation Power Factor Dissipation Factor is addressed in ANSI/NETA ATS-2025.

ProvenanceANSI/NETA ATS-2025 supports data record tests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-ats, which is cited on the entry Insulation Power Factor Dissipation Factor.SOURCEANSI/NETA ATS-2025ANSI/NETA ATS-2025Licensed standard, clause 7.24.1.B.7DATA RECORDtests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-atstests.insulation-power-f..Verified 2026-10-13ENTRYInsulation Power Factor Dissipation FactorInsulation Power Factor ..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/NETA ATS-2025Licensed standard, clause 7.24.1.B.7
Data recordtests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-atsVerified 2026-10-13
EntryInsulation Power Factor Dissipation FactorNo revisions
Subject
Insulation Power Factor Dissipation Factor (Test methods)
Kind
Method fact
Source
ANSI/NETA ATS-2025, clause 7.24.1.B.7, Acceptance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA ATS-2025Publisher information page
Also stated in
  • FIST 4-7, section 6.1.10.2, page 47 (August 2023).
    Read the reference passage

    6.1.10.2 Insulation Test

    "Insulation power factor tests should be the final test prior to energization after all other tests are completed and the switchgear has been thoroughly cleaned to remove all construction dust and debris. Use only fluids or solvents specifically approved by the manufacturer."

    FIST 4-7, section 6.1.10.2, page 47, August 2023. Agency copy of FIST 4-7

    The current standard governs; this passage is a public-domain description of the practice dated August 2023.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-13created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-ats." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/data/tests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-ats/.
Electrical Testing Reference, Data record tests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-ats (Oct. 13, 2026), https://www.electricaltestingreference.com/data/tests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-ats/.
@misc{etr-data-tests-insulation-power-factor-dissipation-factor-governed-by-ansi-neta-ats,
  title = {Data record tests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-ats},
  howpublished = {\url{https://www.electricaltestingreference.com/data/tests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-ats/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {last substantive change 2026-10-13}
}
{{cite web |title=Data record tests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-ats |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/data/tests.insulation-power-factor-dissipation-factor.governed-by.ansi-neta-ats/ |date=2026-10-13 |access-date=}}