Clause 12.2 of IEEE 43-2013 recommends minimum polarization index values that depend on the thermal class of the insulation.

ProvenanceIEEE 43-2013 supports data record tests.polarization-index-and-dielectric-absorption.minimum-shape, which is cited on the entry Polarization Index and Dielectric Absorption.SOURCEIEEE 43-2013IEEE 43-2013Licensed standard, clause 12.2, Table 3DATA RECORDtests.polarization-index-and-dielectric-absorption.minimum-shapetests.polarization-index..Verified 2026-10-13ENTRYPolarization Index and Dielectric AbsorptionPolarization Index and D..1 revision
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceIEEE 43-2013Licensed standard, clause 12.2, Table 3
Data recordtests.polarization-index-and-dielectric-absorption.minimum-shapeVerified 2026-10-13
EntryPolarization Index and Dielectric Absorption1 revision
Subject
Polarization Index and Dielectric Absorption (Test methods)
Kind
Method fact
Source
IEEE 43-2013, clause 12.2, Table 3, Recommended Practice for Testing Insulation Resistance of Electric Machinery, IEEE. Publisher page for IEEE 43-2013Publisher information page
Also stated in
  • TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.g, PDF page 82, printed 5-15, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "deterioration the need" is printed so (29 November 1996).
    Read the reference passage

    5-27.g. Dielectric absorption test

    "This test is usually conducted at higher voltages for extended periods of from 5 to 15 minutes. Since the current is inversely related to time, insulation resistance will rise gradually for a good cable but will flatten rapidly otherwise. Periodic readings should be taken and plotted against time. [...] A polarization index of two or higher indicates good insulation, while a polarization index of less than one indicates cable deterioration the need for immediate maintenance."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.g, PDF page 82, printed 5-15, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "deterioration the need" is printed so, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

  • TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 7-7.b, PDF page 99, printed 7-7, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "of a 2" is printed so (29 November 1996).
    Read the reference passage

    7-7.b. Polarization index (PI) test

    "A PI test or dielectric absorption test is a continuation of the insulation resistance test in which the voltage is applied for a longer period of time. For good insulation, the resistance values will increase with time. [...] An index below 1 indicates poor insulation. An index between 1 and 2 indicates that the insulation is questionable. An index of a 2 and higher indicates good insulation."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 7-7.b, PDF page 99, printed 7-7, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "of a 2" is printed so, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-13created
2026-10-13reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.polarization-index-and-dielectric-absorption.minimum-shape." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/data/tests.polarization-index-and-dielectric-absorption.minimum-shape/.
Electrical Testing Reference, Data record tests.polarization-index-and-dielectric-absorption.minimum-shape (Oct. 13, 2026), https://www.electricaltestingreference.com/data/tests.polarization-index-and-dielectric-absorption.minimum-shape/.
@misc{etr-data-tests-polarization-index-and-dielectric-absorption-minimum-shape,
  title = {Data record tests.polarization-index-and-dielectric-absorption.minimum-shape},
  howpublished = {\url{https://www.electricaltestingreference.com/data/tests.polarization-index-and-dielectric-absorption.minimum-shape/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {last substantive change 2026-10-13}
}
{{cite web |title=Data record tests.polarization-index-and-dielectric-absorption.minimum-shape |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/data/tests.polarization-index-and-dielectric-absorption.minimum-shape/ |date=2026-10-13 |access-date=}}