Polarization Index and Dielectric Absorption
Updated 2026-10-13
| Relationship | Entry |
|---|---|
| Governing standard | ANSI/NETA ATS-2025 (ANSI/NETA ATS-2025 Standard for Acceptance Testing Specifications) |
| Governing standard | ANSI/NETA MTS-2023 (ANSI/NETA MTS-2023 Standard for Maintenance Testing Specifications) |
The polarization index and dielectric absorption test extends the insulation resistance test by taking readings at two different times during a single application of direct voltage and expressing them as a ratio. [1] [2] The polarization index divides the reading at 10 min by the reading at 1 min, while the dielectric absorption ratio uses a pair of readings taken earlier in the test. [3] [4] [5] Both appear in ANSI/NETA ATS-2025 and ANSI/NETA MTS-2023, and IEEE 43-2013 describes the polarization index for the windings of rotating machines. [6] [7] [Motor Testing Reference]
Definition
IEEE 43-2013 defines the polarization index as the insulation resistance measured after the voltage has been applied for 10 min, divided by the insulation resistance measured after 1 min. [1] [3] [4] Annex A of the recommended practice describes variants built on shorter reading times; one of them divides the one-minute reading by a reading taken at 30 s, a ratio of the kind known as the dielectric absorption ratio. [8] [9] [5]
Being ratios of two resistances, both quantities are dimensionless, and the NIST Guide to the SI notes that the unit one is generally left unwritten when such values are stated. [10] [1]
Purpose
The index adds a time dimension to the insulation resistance test. IEEE 43-2013 notes that readings at intervals through the test are commonly recorded so that resistance can be plotted against time, and it reads a sharp fall in the index between tests as a sign of contamination, moisture or cracked insulation. [11] [12] A film of moisture on a winding at or below the dew point lowers both the resistance and the index. [13]
During maintenance the index also serves as a guide to when the drying of a winding can end. [14] IEEE 43-2013 applies no temperature correction to it. [15]
Principle
The index rests on the absorption current, the part of the measured current that dies away while the test voltage is held. [16] Because that component decays, a reading taken late in the test differs from the one-minute reading, and the ratio of the two summarizes how the insulation behaves over the first minutes of voltage application. [1] [16] In small random-wound machines the absorption current decays within a few seconds, which is why IEEE 43-2013 regards the index as not meaningful for them. [17]
Two further conditions limit its use. Where the one-minute resistance at the reference temperature is very high, the measured current becomes so small that the recommended practice allows the index to be disregarded. [18] A continuous stress-control coating over the whole end-winding region can pull the index toward unity. [19]
General procedure
The measurement uses the arrangement of the insulation resistance test: the winding is deenergized, external equipment is disconnected and grounded, and the conditions of the test are recorded. [20] [21] [22] The test voltage is applied and held constant, the one-minute reading and the later reading are taken without interrupting it, and intermediate readings are commonly noted for plotting. [23] [3] [11]
When a hot winding cools during the test and the index comes out high, IEEE 43-2013 calls for the test to be repeated at a lower winding temperature. [15]
Evaluation
Clause 12.2 of IEEE 43-2013 recommends minimum polarization index values that depend on the thermal class of the insulation, and the recommended practice expects a machine to meet both these and its one-minute insulation resistance recommendations before it returns to service or undergoes an overvoltage test. [24] [25] The index is not applied to non-insulated field windings, such as squirrel-cage rotor windings, or to direct-current armatures with exposed commutator copper. [26] Annex A states that no agreed pass or fail criteria exist for the shorter variant ratios. [8]
ANSI/NETA ATS-2025 evaluates polarization index results for rotating machinery in its own text, beginning with section 7.15.1 for AC induction motors and generators, and it also uses a dielectric absorption ratio, which IEEE 43-2013 treats only as an informative variant. [27] [28] The two documents do not set identical criteria in every case, and the numerical criteria are set out in the cited clauses. [27] [24]
Acceptance and maintenance testing
ANSI/NETA ATS-2025 calls for the test at acceptance and ANSI/NETA MTS-2023 in maintenance testing. [6] [7] Among the equipment classes, the acceptance specification lists it for liquid-filled shunt and current-limiting reactors, and the maintenance specification lists it for the same reactors and for induction voltage regulators. [29] [30] [Transformer Testing Reference]
Notes
- IEEE 43-2013, clause 5.4. IEEE 43-2013 defines the polarization index as the insulation resistance read after ten minutes of applied voltage divided by the insulation resistance read after one minute. Datum tests.polarization-index-and-dielectric-absorption.pi-definition
- Electrical Testing Reference editorial taxonomy, 2026-10 edition. The polarization index is the ratio of two insulation resistance readings taken at two times after a direct voltage is applied, the later reading divided by the earlier one. Datum gloss.polarization-index.definition
- IEEE 43-2013, clause 5.4. The later of the two readings that make up the polarization index under IEEE 43-2013 is taken ten minutes after the test voltage is applied. Value: 10 min. Datum tests.polarization-index-and-dielectric-absorption.ten-minute
- IEEE 43-2013, clause 5.3. Under IEEE 43-2013 the reference insulation resistance reading is the one taken when the test voltage has been applied for one minute. Value: 1 min. Datum tests.insulation-resistance.one-minute-reading
- Electrical Testing Reference editorial taxonomy, 2026-10 edition. The dielectric absorption ratio is the ratio of two insulation resistance readings taken a short time apart early in a direct-voltage test, the later reading divided by the earlier one. Datum gloss.dielectric-absorption-ratio.definition
- ANSI/NETA ATS-2025, clause 7.20.3.2.B.2. Polarization Index and Dielectric Absorption is addressed in ANSI/NETA ATS-2025. Datum tests.polarization-index-and-dielectric-absorption.governed-by.ansi-neta-ats(provenance pending)
- ANSI/NETA MTS-2023, clause 7.20.3.2.B. Polarization Index and Dielectric Absorption is addressed in ANSI/NETA MTS-2023. Datum tests.polarization-index-and-dielectric-absorption.governed-by.ansi-neta-mts(provenance pending)
- IEEE 43-2013, clause Annex A. Annex A of IEEE 43-2013 describes variants of the polarization index built on shorter reading times and states that no agreed pass or fail criteria exist for them. Datum tests.polarization-index-and-dielectric-absorption.annex-variants
- IEEE 43-2013, clause A.1. One variant in Annex A of IEEE 43-2013 divides the one-minute insulation resistance by a reading taken thirty seconds after the voltage is applied. Value: 30 s. Datum tests.polarization-index-and-dielectric-absorption.dar-thirty-second
- NIST SP 811, web page updated 2025-08-18 edition, clause Table 3, note b. The NIST Guide to the SI notes that the symbol for the derived unit one is generally omitted when values of dimensionless quantities are stated. Datum qty.dissipation-factor.unit-one
- IEEE 43-2013, clause 5.4. IEEE 43-2013 notes that readings at several intervals during the test are commonly recorded so that resistance can be plotted against time. Datum tests.polarization-index-and-dielectric-absorption.intermediate-readings
- IEEE 43-2013, clause 11.1. IEEE 43-2013 reads a sharp fall in the polarization index between tests, like a sharp fall in the one-minute insulation resistance, as a sign of contamination, moisture or cracked insulation. Datum tests.polarization-index-and-dielectric-absorption.trend-fall
- IEEE 43-2013, clause 6.2, 6.3.1. IEEE 43-2013 notes that when a winding is at or below the dew point a film of moisture can form on it and lower both the insulation resistance and the polarization index. Datum tests.insulation-resistance.dew-point
- IEEE 43-2013, clause 11.2. IEEE 43-2013 notes that the polarization index can indicate when the drying of a winding may be stopped. Datum tests.polarization-index-and-dielectric-absorption.drying
- IEEE 43-2013, clause 6.3.4, 11.1. IEEE 43-2013 applies no temperature correction to the polarization index, and it calls for a repeat test at a lower temperature when a hot winding that cooled during the test gives a high result. Datum tests.polarization-index-and-dielectric-absorption.no-temperature-correction
- IEEE 43-2013, clause 5.4. IEEE 43-2013 links the usefulness of the polarization index to the absorption current, the part of the measured current that dies away while the voltage is held, so the index loses its meaning where that current disappears within seconds. Datum tests.polarization-index-and-dielectric-absorption.absorption-current
- IEEE 43-2013, clause 5.4. IEEE 43-2013 regards the polarization index as not meaningful for small random-wound machines, because their absorption current dies away within a few seconds. Datum tests.polarization-index-and-dielectric-absorption.small-machines
- IEEE 43-2013, clause 12.2.2. When the one-minute insulation resistance at the reference temperature is very high, the measured current is so small that IEEE 43-2013 allows the polarization index to be disregarded. Datum tests.polarization-index-and-dielectric-absorption.high-ir-disregard
- IEEE 43-2013, clause 12.2.3. IEEE 43-2013 notes that a continuous stress-control coating over the whole end-winding region can pull the polarization index toward unity. Datum tests.polarization-index-and-dielectric-absorption.stress-control
- 29 CFR 1910.333, current edition, clause 1910.333(a)(1). Under 29 CFR 1910.333(a)(1), live parts to which an employee may be exposed are to be deenergized before the employee works on or near them, unless the employer shows that deenergizing creates added hazards or is infeasible. Datum tests.insulation-resistance.osha-deenergize
- IEEE 43-2013, clause 8. IEEE 43-2013 has cables, surge arresters, capacitors, voltage transformers and similar external equipment disconnected from the winding and grounded before the test, with any item left connected noted in the record. Datum tests.insulation-resistance.external-equipment
- IEEE 43-2013, clause 7. IEEE 43-2013 lists what is recorded with each test, among them the winding temperature, the temperature, humidity and dew point of the surrounding air, how long the machine has been out of service, the voltage applied and how the winding was connected. Datum tests.insulation-resistance.records
- IEEE 43-2013, clause 10. IEEE 43-2013 brings the test voltage to its full value as quickly as practical and keeps it constant for the whole measurement. Datum tests.insulation-resistance.voltage-application
- IEEE 43-2013, clause 12.2, Table 3. Clause 12.2 of IEEE 43-2013 recommends minimum polarization index values that depend on the thermal class of the insulation. Datum tests.polarization-index-and-dielectric-absorption.minimum-shape
- IEEE 43-2013, clause 11.2. IEEE 43-2013 expects a machine to clear both its polarization index and its one-minute insulation resistance recommendations before it is returned to operation or given an overvoltage test. Datum tests.polarization-index-and-dielectric-absorption.both-minimums
- IEEE 43-2013, clause 12.2.1. IEEE 43-2013 does not apply the polarization index to non-insulated field windings, such as squirrel-cage rotor windings, or to direct-current armatures with exposed commutator copper. Datum tests.polarization-index-and-dielectric-absorption.not-applicable
- ANSI/NETA ATS-2025, clause 7.15.1.D.2. ANSI/NETA ATS-2025 section 7.15.1 evaluates polarization index results for AC induction motors and generators in its own text, and its criteria do not coincide in every case with the minimums recommended in IEEE 43-2013. Datum tests.polarization-index-and-dielectric-absorption.ats-rotating
- ANSI/NETA ATS-2025, clause 7.15.1.B.2. ANSI/NETA ATS-2025 uses a dielectric absorption ratio for rotating machinery, a measure that IEEE 43-2013 describes only as an informative variant. Datum tests.polarization-index-and-dielectric-absorption.ats-dar
- ANSI/NETA ATS-2025, clause 7.20.3.2.B.2. Polarization Index and Dielectric Absorption is specified for liquid-filled shunt and current-limiting reactors in acceptance testing at clause 7.20.3.2.B.2 of ANSI/NETA ATS-2025. Value: liquid-filled shunt and current-limiting reactors. Datum tests.polarization-index-and-dielectric-absorption.equipment.reactor.acceptance(provenance pending)
- ANSI/NETA MTS-2023, clause 7.20.3.2.B. Polarization Index and Dielectric Absorption is specified for liquid-filled shunt and current-limiting reactors in maintenance testing at clause 7.20.3.2.B of ANSI/NETA MTS-2023. Value: liquid-filled shunt and current-limiting reactors. Datum tests.polarization-index-and-dielectric-absorption.equipment.reactor.maintenance(provenance pending)
Data records
- IEEE 43-2013 links the usefulness of the polarization index to the absorption current, the part of the measured current that dies away while the voltage is held, so the index loses its meaning where that current disappears within seconds.
- Annex A of IEEE 43-2013 describes variants of the polarization index built on shorter reading times and states that no agreed pass or fail criteria exist for them.
- ANSI/NETA ATS-2025 uses a dielectric absorption ratio for rotating machinery, a measure that IEEE 43-2013 describes only as an informative variant.
- ANSI/NETA ATS-2025 section 7.15.1 evaluates polarization index results for AC induction motors and generators in its own text, and its criteria do not coincide in every case with the minimums recommended in IEEE 43-2013.
- IEEE 43-2013 expects a machine to clear both its polarization index and its one-minute insulation resistance recommendations before it is returned to operation or given an overvoltage test.
- One variant in Annex A of IEEE 43-2013 divides the one-minute insulation resistance by a reading taken thirty seconds after the voltage is applied. Value: 30 s.
- IEEE 43-2013 notes that the polarization index can indicate when the drying of a winding may be stopped.
- Polarization Index and Dielectric Absorption is specified for liquid-filled shunt and current-limiting reactors in acceptance testing at clause 7.20.3.2.B.2 of ANSI/NETA ATS-2025. Value: liquid-filled shunt and current-limiting reactors.
- Polarization Index and Dielectric Absorption is specified for liquid-filled shunt and current-limiting reactors in maintenance testing at clause 7.20.3.2.B of ANSI/NETA MTS-2023. Value: liquid-filled shunt and current-limiting reactors.
- Polarization Index and Dielectric Absorption is addressed in ANSI/NETA ATS-2025.
- Polarization Index and Dielectric Absorption is addressed in ANSI/NETA MTS-2023.
- When the one-minute insulation resistance at the reference temperature is very high, the measured current is so small that IEEE 43-2013 allows the polarization index to be disregarded.
- IEEE 43-2013 notes that readings at several intervals during the test are commonly recorded so that resistance can be plotted against time.
- Clause 12.2 of IEEE 43-2013 recommends minimum polarization index values that depend on the thermal class of the insulation.
- IEEE 43-2013 applies no temperature correction to the polarization index, and it calls for a repeat test at a lower temperature when a hot winding that cooled during the test gives a high result.
- IEEE 43-2013 does not apply the polarization index to non-insulated field windings, such as squirrel-cage rotor windings, or to direct-current armatures with exposed commutator copper.
- IEEE 43-2013 defines the polarization index as the insulation resistance read after ten minutes of applied voltage divided by the insulation resistance read after one minute.
- IEEE 43-2013 regards the polarization index as not meaningful for small random-wound machines, because their absorption current dies away within a few seconds.
- IEEE 43-2013 notes that a continuous stress-control coating over the whole end-winding region can pull the polarization index toward unity.
- The later of the two readings that make up the polarization index under IEEE 43-2013 is taken ten minutes after the test voltage is applied. Value: 10 min.
- The test method is named Polarization Index and Dielectric Absorption. Value: Polarization Index and Dielectric Absorption.
- IEEE 43-2013 reads a sharp fall in the polarization index between tests, like a sharp fall in the one-minute insulation resistance, as a sign of contamination, moisture or cracked insulation.
Elsewhere in the family
- Polarization Index and Dielectric Absorption more on this entry on Transformer Testing Reference
- Step voltage test related entry on Test Instrument Reference
- Absorption current related entry on Test Instrument Reference
- Insulation resistance tester related entry on Test Instrument Reference
Sources
- 29 CFR 1910.333, 1910.333 - Selection and use of work practices, current edition, OSHA. Cited: clause 1910.333(a)(1). Regulation text. Held as: Government work. Agency copy of 29 CFR 1910.333
- ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 7.20.3.2.B.2; clause 7.15.1.D.2; clause 7.15.1.B.2. Held as: Purchased single-user copy. Publisher page for ANSI/NETA ATS-2025Publisher information page
- ANSI/NETA MTS-2023, Maintenance Testing Specifications for Electrical Power Equipment and Systems, 2023 edition, NETA. Cited: clause 7.20.3.2.B. Held as: Purchased single-user copy. Publisher page for ANSI/NETA MTS-2023Publisher information page
- Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
- IEEE 43-2013, Recommended Practice for Testing Insulation Resistance of Electric Machinery, 2013 edition, IEEE. Cited: clause 5.4; clause 5.3; clause A.1; clause Annex A; clause 11.1; clause 6.2, 6.3.1; clause 11.2; clause 6.3.4, 11.1; clause 12.2.2; clause 12.2.3; clause 8; clause 7; clause 10; clause 12.2, Table 3; clause 12.2.1. Held as: Purchased single-user copy. Publisher page for IEEE 43-2013Publisher information page
- NIST SP 811, NIST Guide to the SI, Chapter 4: The Two Classes of SI Units and the SI Prefixes, web page updated 2025-08-18 edition, NIST. Cited: clause Table 3, note b. Agency document. Held as: Government work. Agency copy of NIST SP 811
Also stated in
- FIST 4-7, section 6.1.28, page 84 (August 2023).
Read the reference passage
6.1.28 Generator and Large Motor Windings
"A polarization index test is similar to the insulation resistance test except that current (or resistance) readings are taken at two intervals, normally one and ten minutes after application of the voltage step. [...] A stator winding may fail the PI test if it has absorbed significant moisture, has substantial surface contamination, or major physical damage. Prior to performing ac or dc high-potential acceptance testing, the winding must pass the PI test."
FIST 4-7, section 6.1.28, page 84, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
- FIST 4-7, section 6.1.8.1, page 38 (August 2023).
Read the reference passage
6.1.8.1 Insulation Resistance and Polarization Index (PI) Testing
"To perform a test, a specified high, direct voltage is applied to the test specimen and held for 10 minutes. At the 1- and 10-minute intervals, the insulation resistance and/or current are recorded. The insulation resistance is the value recorded at the 1-minute interval. Often the value will be corrected to a normalized temperature of 40 °C."
FIST 4-7, section 6.1.8.1, page 38, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
- Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.g, PDF page 82, printed 5-15, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "deterioration the need" is printed so (29 November 1996).
Read the reference passage
5-27.g. Dielectric absorption test
"This test is usually conducted at higher voltages for extended periods of from 5 to 15 minutes. Since the current is inversely related to time, insulation resistance will rise gradually for a good cable but will flatten rapidly otherwise. Periodic readings should be taken and plotted against time. [...] A polarization index of two or higher indicates good insulation, while a polarization index of less than one indicates cable deterioration the need for immediate maintenance."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.g, PDF page 82, printed 5-15, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "deterioration the need" is printed so, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 7-7.b, PDF page 99, printed 7-7, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "of a 2" is printed so (29 November 1996).
Read the reference passage
7-7.b. Polarization index (PI) test
"A PI test or dielectric absorption test is a continuation of the insulation resistance test in which the voltage is applied for a longer period of time. For good insulation, the resistance values will increase with time. [...] An index below 1 indicates poor insulation. An index between 1 and 2 indicates that the insulation is questionable. An index of a 2 and higher indicates good insulation."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 7-7.b, PDF page 99, printed 7-7, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "of a 2" is printed so, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- FIST 4-7, section 6.1.8.1, page 37 (August 2023).
Read the reference passage
6.1.8.1 Insulation Resistance and Polarization Index (PI) Testing
"Insulation resistance and PI testing applies a high, direct-voltage to the test specimen and measures the corresponding current through the insulation system of interest. These tests must be successfully completed prior to performing a high-potential withstand (proof) test, also known as a 'hipot' test. If the test specimen yields poor insulation resistance or unacceptable polarization index results, the problem must be identified and corrected, and the specimen must pass a repeat testing prior to performing final high-potential withstand test."
FIST 4-7, section 6.1.8.1, page 37, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
- FIST 4-7, section 6.1.28, page 86 (August 2023).
Read the reference passage
6.1.28 Generator and Large Motor Windings
"Field windings often do not achieve the same polarization index values as stator windings because they utilize different insulation components, often with lower polarizability. Thus, the same metrics applied to stator windings may not always apply to field winding insulation systems."
FIST 4-7, section 6.1.28, page 86, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
- EM 385-1-1, section 11-4.c(4), page 212, the trailing cross-reference to 11-8.e(4) left off (15 March 2024).
Read the reference passage
11-4. Roles and Responsibilities. c. Host Employer
"If work must be performed on an energized system, then the host employer or system owner must first demonstrate that de-energizing introduces additional or increased hazards (for example, interruption of life support equipment, removal of light for an area) or is infeasible due to equipment design or operational limitations (for example, testing, troubleshooting)."
EM 385-1-1, section 11-4.c(4), page 212, the trailing cross-reference to 11-8.e(4) left off, 15 March 2024. Agency copy of EM 385-1-1
The current standard governs; this passage is a public-domain description of the practice dated 15 March 2024.
- EM 385-1-1, section 11-8.d, page 223, the paragraph's citation anchor kept inside the run; the ellipsis drops step (5), the test of each phase conductor with an adequately rated instrument, which names a standard (15 March 2024).
Read the reference passage
11-8. General Requirements. d. Establishing an Electrically Safe Work Condition (ESWC)
"All equipment and circuits must be de-energized before work is started unless energized work can be justified. A QP must complete and verify the following to establish electrically safe working conditions: (11-8.d) [...] (2) Control all sources of electrical energy to minimize employee exposure to electrical hazards. (3) Visually verify the disconnecting device is open or circuit breaker is withdrawn whenever possible. (4) Apply HEC devices (see chapter 12). [...] (6) Where induced voltages are possible, stored electrical energy exists, or if required within this chapter, ground the conductors or circuit parts before touching them."
EM 385-1-1, section 11-8.d, page 223, the paragraph's citation anchor kept inside the run; the ellipsis drops step (5), the test of each phase conductor with an adequately rated instrument, which names a standard, 15 March 2024. Agency copy of EM 385-1-1
The current standard governs; this passage is a public-domain description of the practice dated 15 March 2024.
- TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.g, PDF page 82, printed 5-15, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "deterioration the need" is printed so (29 November 1996).
Read the reference passage
5-27.g. Dielectric absorption test
"This test is usually conducted at higher voltages for extended periods of from 5 to 15 minutes. Since the current is inversely related to time, insulation resistance will rise gradually for a good cable but will flatten rapidly otherwise. Periodic readings should be taken and plotted against time. [...] A polarization index of two or higher indicates good insulation, while a polarization index of less than one indicates cable deterioration the need for immediate maintenance."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-27.g, PDF page 82, printed 5-15, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "deterioration the need" is printed so, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 7-7.b, PDF page 99, printed 7-7, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "of a 2" is printed so (29 November 1996).
Read the reference passage
7-7.b. Polarization index (PI) test
"A PI test or dielectric absorption test is a continuation of the insulation resistance test in which the voltage is applied for a longer period of time. For good insulation, the resistance values will increase with time. [...] An index below 1 indicates poor insulation. An index between 1 and 2 indicates that the insulation is questionable. An index of a 2 and higher indicates good insulation."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 7-7.b, PDF page 99, printed 7-7, the ellipsis drops the sentence defining the index as the 10-minute to 1-minute ratio, whose OCR is broken; "of a 2" is printed so, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
Obtaining the documents
- ANSI/NETA ATS-2025: available from the publisher
- ANSI/NETA MTS-2023: available from the publisher
- IEEE 43-2013: available from the publisher
Changelog (56 entries)
| Date | Revision | Change |
|---|---|---|
| 2026-10-13 | created (gloss.dielectric-absorption-ratio.definition) | |
| 2026-10-13 | reviewed (gloss.dielectric-absorption-ratio.definition) | |
| 2026-10-13 | created (gloss.polarization-index.definition) | |
| 2026-10-13 | reviewed (gloss.polarization-index.definition) | |
| 2026-10-13 | 1 | created |
| 2026-10-13 | created (qty.dissipation-factor.unit-one) | |
| 2026-10-13 | reviewed (qty.dissipation-factor.unit-one) | |
| 2026-10-13 | created (tests.insulation-resistance.dew-point) | |
| 2026-10-13 | reviewed (tests.insulation-resistance.dew-point) | |
| 2026-10-13 | created (tests.insulation-resistance.external-equipment) | |
| 2026-10-13 | reviewed (tests.insulation-resistance.external-equipment) | |
| 2026-10-13 | created (tests.insulation-resistance.one-minute-reading) | |
| 2026-10-13 | reviewed (tests.insulation-resistance.one-minute-reading) | |
| 2026-10-13 | created (tests.insulation-resistance.osha-deenergize) | |
| 2026-10-13 | reviewed (tests.insulation-resistance.osha-deenergize) | |
| 2026-10-13 | created (tests.insulation-resistance.records) | |
| 2026-10-13 | reviewed (tests.insulation-resistance.records) | |
| 2026-10-13 | created (tests.insulation-resistance.voltage-application) | |
| 2026-10-13 | reviewed (tests.insulation-resistance.voltage-application) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.absorption-current) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.absorption-current) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.annex-variants) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.annex-variants) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.ats-dar) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.ats-rotating) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.both-minimums) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.both-minimums) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.dar-thirty-second) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.dar-thirty-second) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.drying) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.drying) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.equipment.reactor.acceptance) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.equipment.reactor.maintenance) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.governed-by.ansi-neta-ats) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.governed-by.ansi-neta-mts) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.high-ir-disregard) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.high-ir-disregard) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.intermediate-readings) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.intermediate-readings) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.minimum-shape) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.minimum-shape) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.no-temperature-correction) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.no-temperature-correction) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.not-applicable) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.not-applicable) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.pi-definition) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.pi-definition) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.small-machines) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.small-machines) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.stress-control) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.stress-control) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.ten-minute) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.ten-minute) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.title) | |
| 2026-10-13 | created (tests.polarization-index-and-dielectric-absorption.trend-fall) | |
| 2026-10-13 | reviewed (tests.polarization-index-and-dielectric-absorption.trend-fall) |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
Permanent revision URL: https://www.electricaltestingreference.com/tests/polarization-index-and-dielectric-absorption/rev/1/. Current version: https://www.electricaltestingreference.com/tests/polarization-index-and-dielectric-absorption/.
"Polarization Index and Dielectric Absorption." Electrical Testing Reference. Revision 1, 2026-10-13. https://www.electricaltestingreference.com/tests/polarization-index-and-dielectric-absorption/rev/1/.
Electrical Testing Reference, Polarization Index and Dielectric Absorption (rev. 1, Oct. 13, 2026), https://www.electricaltestingreference.com/tests/polarization-index-and-dielectric-absorption/rev/1/.
@misc{etr-tests-polarization-index-and-dielectric-absorption-rev1,
title = {Polarization Index and Dielectric Absorption},
howpublished = {\url{https://www.electricaltestingreference.com/tests/polarization-index-and-dielectric-absorption/rev/1/}},
organization = {Electrical Testing Reference},
publisher = {Electrical Testing Reference},
year = {2026},
note = {Revision 1; last substantive change 2026-10-13}
}{{cite web |title=Polarization Index and Dielectric Absorption |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/tests/polarization-index-and-dielectric-absorption/rev/1/ |date=2026-10-13 |access-date= |version=1}}