Data record tests.surge-arrester-and-spd-tests.equipment.surge.maintenance

Verified 2026-10-13 Confidence: Medium

Provenance pending: the source of this record has not yet been confirmed as official.

Surge Arrester and SPD Tests is specified for medium-voltage and high-voltage surge arresters in maintenance testing at clause 7.19.2.B of ANSI/NETA MTS-2023.

Value: medium-voltage and high-voltage surge arresters

ProvenanceANSI/NETA MTS-2023 supports data record tests.surge-arrester-and-spd-tests.equipment.surge.maintenance, which is cited on the entry Surge Arrester and SPD Tests.SOURCEANSI/NETA MTS-2023ANSI/NETA MTS-2023Licensed standard, clause 7.19.2.BDATA RECORDtests.surge-arrester-and-spd-tests.equipment.surge.maintenancetests.surge-arrester-and..Verified 2026-10-13ENTRYSurge Arrester and SPD TestsSurge Arrester and SPD T..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/NETA MTS-2023Licensed standard, clause 7.19.2.B
Data recordtests.surge-arrester-and-spd-tests.equipment.surge.maintenanceVerified 2026-10-13
EntrySurge Arrester and SPD TestsNo revisions
Subject
Surge Arrester and SPD Tests (Test methods)
Kind
Equipment fact
Source
ANSI/NETA MTS-2023, clause 7.19.2.B, Maintenance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA MTS-2023Publisher information page
Also stated in
  • TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8.b, PDF page 117, printed 9-2 (29 November 1996).
    Read the reference passage

    9-8.b. Electrical tests

    "Visual inspection will not always detect a damaged arrester. Interior damage may result from a broken element, presence of moisture, a severe direct lightning stroke, or the use of an arrester with an incorrect rating. Sometimes these conditions will cause radio interference. Electrical tests, to detect inferior arrester units, may be made either in the field or shop. Tests must be made strictly in accordance with manufacturer's recommendations, and the results interpreted in line with manufacturer's criteria."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8.b, PDF page 117, printed 9-2, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

  • Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8.b, PDF page 117, printed 9-2, item (1) (29 November 1996).
    Read the reference passage

    9-8.b(1). Power factor tests

    "Each type and class of lightning arrester has a specific power factor when new. Periodic testing of a unit will show little deviation from the original (when new) power factor, so long as it remains in good operating condition. A major deviation from the original value indicates that the arrester has been mechanically damaged or contains moisture."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8.b, PDF page 117, printed 9-2, item (1), 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

  • Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8, PDF page 117, printed 9-2 (29 November 1996).
    Read the reference passage

    9-8. Maintenance of surge arresters

    "Modern surge arresters require little operational maintenance and the degree to which such maintenance can be done is normally limited by lack of adequate test equipment. This limits surge arrester maintenance to visual inspection and simple electrical tests. It is recommended that units found to be defective be replaced rather than repaired: Where an arrester is composed of two or more individually complete units, each unit should be tested separately. Thus, a bad unit may readily be replaced and the good units retained. Surge arresters are almost always applied with one terminal connected to an electrically energized source and one terminal to ground. No work should be done, or contact made with surge arresters, when connected to the energized source."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8, PDF page 117, printed 9-2, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-13created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.surge-arrester-and-spd-tests.equipment.surge.maintenance." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/data/tests.surge-arrester-and-spd-tests.equipment.surge.maintenance/.
Electrical Testing Reference, Data record tests.surge-arrester-and-spd-tests.equipment.surge.maintenance (Oct. 13, 2026), https://www.electricaltestingreference.com/data/tests.surge-arrester-and-spd-tests.equipment.surge.maintenance/.
@misc{etr-data-tests-surge-arrester-and-spd-tests-equipment-surge-maintenance,
  title = {Data record tests.surge-arrester-and-spd-tests.equipment.surge.maintenance},
  howpublished = {\url{https://www.electricaltestingreference.com/data/tests.surge-arrester-and-spd-tests.equipment.surge.maintenance/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {last substantive change 2026-10-13}
}
{{cite web |title=Data record tests.surge-arrester-and-spd-tests.equipment.surge.maintenance |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/data/tests.surge-arrester-and-spd-tests.equipment.surge.maintenance/ |date=2026-10-13 |access-date=}}