Surge Arrester and SPD Tests
Updated 2026-10-13
| Relationship | Entry |
|---|---|
| Governing standard | ANSI/NETA ATS-2025 (ANSI/NETA ATS-2025 Standard for Acceptance Testing Specifications) |
| Governing standard | ANSI/NETA MTS-2023 (ANSI/NETA MTS-2023 Standard for Maintenance Testing Specifications) |
Data records
- Surge Arrester and SPD Tests is specified for medium-voltage and high-voltage surge arresters in acceptance testing at clause 7.19.2.B.4 of ANSI/NETA ATS-2025. Value: medium-voltage and high-voltage surge arresters.
- Surge Arrester and SPD Tests is specified for medium-voltage and high-voltage surge arresters in maintenance testing at clause 7.19.2.B of ANSI/NETA MTS-2023. Value: medium-voltage and high-voltage surge arresters.
- Surge Arrester and SPD Tests is addressed in ANSI/NETA ATS-2025.
- Surge Arrester and SPD Tests is addressed in ANSI/NETA MTS-2023.
- The test method is named Surge Arrester and SPD Tests. Value: Surge Arrester and SPD Tests.
Elsewhere in the family
- Surge Arrester and SPD Tests more on this entry on Motor Testing Reference
- Surge Arrester and SPD Tests more on this entry on Switchgear Testing Reference
- Surge Arrester and SPD Tests more on this entry on Transformer Testing Reference
- Arc Energy Reduction Performance related entry on Arc Flash Reference
- Primary Current Injection Trip Test related entry on Circuit Breaker Reference
- Protective Relay Element Tests related entry on Protective Relay Reference
Sources
- ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 7.19.2.B.4; clause 7.15.1.B.9. Held as: Purchased single-user copy. Publisher page for ANSI/NETA ATS-2025Publisher information page
- ANSI/NETA MTS-2023, Maintenance Testing Specifications for Electrical Power Equipment and Systems, 2023 edition, NETA. Cited: clause 7.19.2.B; clause 7.15.2.B. Held as: Purchased single-user copy. Publisher page for ANSI/NETA MTS-2023Publisher information page
- Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
Also stated in
- TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8.b, PDF page 117, printed 9-2 (29 November 1996).
Read the reference passage
9-8.b. Electrical tests
"Visual inspection will not always detect a damaged arrester. Interior damage may result from a broken element, presence of moisture, a severe direct lightning stroke, or the use of an arrester with an incorrect rating. Sometimes these conditions will cause radio interference. Electrical tests, to detect inferior arrester units, may be made either in the field or shop. Tests must be made strictly in accordance with manufacturer's recommendations, and the results interpreted in line with manufacturer's criteria."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8.b, PDF page 117, printed 9-2, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8.b, PDF page 117, printed 9-2, item (1) (29 November 1996).
Read the reference passage
9-8.b(1). Power factor tests
"Each type and class of lightning arrester has a specific power factor when new. Periodic testing of a unit will show little deviation from the original (when new) power factor, so long as it remains in good operating condition. A major deviation from the original value indicates that the arrester has been mechanically damaged or contains moisture."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8.b, PDF page 117, printed 9-2, item (1), 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8, PDF page 117, printed 9-2 (29 November 1996).
Read the reference passage
9-8. Maintenance of surge arresters
"Modern surge arresters require little operational maintenance and the degree to which such maintenance can be done is normally limited by lack of adequate test equipment. This limits surge arrester maintenance to visual inspection and simple electrical tests. It is recommended that units found to be defective be replaced rather than repaired: Where an arrester is composed of two or more individually complete units, each unit should be tested separately. Thus, a bad unit may readily be replaced and the good units retained. Surge arresters are almost always applied with one terminal connected to an electrically energized source and one terminal to ground. No work should be done, or contact made with surge arresters, when connected to the energized source."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8, PDF page 117, printed 9-2, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
Obtaining the documents
- ANSI/NETA ATS-2025: available from the publisher
- ANSI/NETA MTS-2023: available from the publisher
Changelog (5 entries)
| Date | Revision | Change |
|---|---|---|
| 2026-10-13 | created (tests.surge-arrester-and-spd-tests.equipment.surge.acceptance) | |
| 2026-10-13 | created (tests.surge-arrester-and-spd-tests.equipment.surge.maintenance) | |
| 2026-10-13 | created (tests.surge-arrester-and-spd-tests.governed-by.ansi-neta-ats) | |
| 2026-10-13 | created (tests.surge-arrester-and-spd-tests.governed-by.ansi-neta-mts) | |
| 2026-10-13 | created (tests.surge-arrester-and-spd-tests.title) |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Surge Arrester and SPD Tests." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/tests/surge-arrester-and-spd-tests/.
Electrical Testing Reference, Surge Arrester and SPD Tests (Oct. 13, 2026), https://www.electricaltestingreference.com/tests/surge-arrester-and-spd-tests/.
@misc{etr-tests-surge-arrester-and-spd-tests,
title = {Surge Arrester and SPD Tests},
howpublished = {\url{https://www.electricaltestingreference.com/tests/surge-arrester-and-spd-tests/}},
organization = {Electrical Testing Reference},
publisher = {Electrical Testing Reference},
year = {2026},
note = {last substantive change 2026-10-13}
}{{cite web |title=Surge Arrester and SPD Tests |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/tests/surge-arrester-and-spd-tests/ |date=2026-10-13 |access-date=}}