Data record tests.visual-and-mechanical-inspection.equipment.arrester-mv-hv.maintenance

Verified 2026-11-02 Confidence: High

Visual and Mechanical Inspection is specified for medium-voltage and high-voltage surge arresters in maintenance testing at clause 7.19.2.A of ANSI/NETA MTS-2023. The clause covers the physical and mechanical condition, anchorage, alignment and grounding, cleaning, bolted connections, the ground lead of each device individually attached to a ground bus or ground electrode, and the mounting and electrical connection of a stroke counter where one is fitted, with as-found and as-left tests around the cleaning.

Value: medium-voltage and high-voltage surge arresters

ProvenanceANSI/NETA MTS-2023 supports data record tests.visual-and-mechanical-inspection.equipment.arrester-mv-hv.maintenance, which is cited on the entry Visual and Mechanical Inspection.SOURCEANSI/NETA MTS-2023ANSI/NETA MTS-2023Licensed standard, clause 7.19.2.ADATA RECORDtests.visual-and-mechanical-inspection.equipment.arrester-mv-hv.maintenancetests.visual-and-mechani..Verified 2026-11-02ENTRYVisual and Mechanical InspectionVisual and Mechanical In..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/NETA MTS-2023Licensed standard, clause 7.19.2.A
Data recordtests.visual-and-mechanical-inspection.equipment.arrester-mv-hv.maintenanceVerified 2026-11-02
EntryVisual and Mechanical InspectionNo revisions
Subject
Visual and Mechanical Inspection (Test methods)
Kind
Equipment fact
Source
ANSI/NETA MTS-2023, clause 7.19.2.A, Maintenance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA MTS-2023Publisher information page
Also stated in
  • TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8.a, PDF page 117, printed 9-2, items (1) to (3) of five (29 November 1996).
    Read the reference passage

    9-8.a. Visual inspections

    "Visual inspection should be made periodically to ensure that: (1) The line lead is securely fastened to the line conductor and the arrester. (2) The ground lead is securely fastened to the arrester terminal and ground. (3) The arrester housing is clean and free from cracks, chips, or evidence of external flashover."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 9-8.a, PDF page 117, printed 9-2, items (1) to (3) of five, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.