Dielectric absorption ratio

Updated 2026-10-13

The dielectric absorption ratio is the ratio of two insulation resistance readings taken a short interval apart early in a direct-voltage test, the later reading divided by the earlier one. [1] Annex A of IEEE 43-2013 describes a ratio of this kind that divides the one-minute reading by a reading taken at 30 s. [2]

Usage

IEEE 43-2013 treats such shorter-time ratios as informative variants of the polarization index and states that no agreed pass or fail criteria exist for them. [3] ANSI/NETA ATS-2025 nevertheless uses a dielectric absorption ratio in evaluating rotating machinery. [4]

See also

Related entries are the polarization index, formed from readings at 10 min and 1 min, and insulation resistance. [5] [6]

Notes

  1. Electrical Testing Reference editorial taxonomy, 2026-10 edition. The dielectric absorption ratio is the ratio of two insulation resistance readings taken a short time apart early in a direct-voltage test, the later reading divided by the earlier one. Datum gloss.dielectric-absorption-ratio.definition
  2. IEEE 43-2013, clause A.1. One variant in Annex A of IEEE 43-2013 divides the one-minute insulation resistance by a reading taken thirty seconds after the voltage is applied. Value: 30 s. Datum tests.polarization-index-and-dielectric-absorption.dar-thirty-second
  3. IEEE 43-2013, clause Annex A. Annex A of IEEE 43-2013 describes variants of the polarization index built on shorter reading times and states that no agreed pass or fail criteria exist for them. Datum tests.polarization-index-and-dielectric-absorption.annex-variants
  4. ANSI/NETA ATS-2025, clause 7.15.1.B.2. ANSI/NETA ATS-2025 uses a dielectric absorption ratio for rotating machinery, a measure that IEEE 43-2013 describes only as an informative variant. Datum tests.polarization-index-and-dielectric-absorption.ats-dar
  5. IEEE 43-2013, clause 5.4. IEEE 43-2013 defines the polarization index as the insulation resistance read after ten minutes of applied voltage divided by the insulation resistance read after one minute. Datum tests.polarization-index-and-dielectric-absorption.pi-definition
  6. IEEE 43-2013, clause 5.4. The later of the two readings that make up the polarization index under IEEE 43-2013 is taken ten minutes after the test voltage is applied. Value: 10 min. Datum tests.polarization-index-and-dielectric-absorption.ten-minute

Data records

  • The dielectric absorption ratio is the ratio of two insulation resistance readings taken a short time apart early in a direct-voltage test, the later reading divided by the earlier one. Source: Electrical Testing Reference editorial taxonomy, 2026-10 edition. Verified 2026-10-13. Record gloss.dielectric-absorption-ratio.definition

Sources

  • ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 7.15.1.B.2. Held as: Purchased single-user copy. Publisher page for ANSI/NETA ATS-2025Publisher information page
  • Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
  • IEEE 43-2013, Recommended Practice for Testing Insulation Resistance of Electric Machinery, 2013 edition, IEEE. Cited: clause A.1; clause Annex A; clause 5.4; clause 5.3. Held as: Purchased single-user copy. Publisher page for IEEE 43-2013Publisher information page

Obtaining the documents

Changelog (14 entries)
DateRevisionChange
2026-10-13created (gloss.dielectric-absorption-ratio.definition)
2026-10-13reviewed (gloss.dielectric-absorption-ratio.definition)
2026-10-131created
2026-10-13created (tests.insulation-resistance.one-minute-reading)
2026-10-13reviewed (tests.insulation-resistance.one-minute-reading)
2026-10-13created (tests.polarization-index-and-dielectric-absorption.annex-variants)
2026-10-13reviewed (tests.polarization-index-and-dielectric-absorption.annex-variants)
2026-10-13created (tests.polarization-index-and-dielectric-absorption.ats-dar)
2026-10-13created (tests.polarization-index-and-dielectric-absorption.dar-thirty-second)
2026-10-13reviewed (tests.polarization-index-and-dielectric-absorption.dar-thirty-second)
2026-10-13created (tests.polarization-index-and-dielectric-absorption.pi-definition)
2026-10-13reviewed (tests.polarization-index-and-dielectric-absorption.pi-definition)
2026-10-13created (tests.polarization-index-and-dielectric-absorption.ten-minute)
2026-10-13reviewed (tests.polarization-index-and-dielectric-absorption.ten-minute)

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

Permanent revision URL: https://www.electricaltestingreference.com/glossary/dielectric-absorption-ratio/rev/1/. Current version: https://www.electricaltestingreference.com/glossary/dielectric-absorption-ratio/.

"Dielectric absorption ratio." Electrical Testing Reference. Revision 1, 2026-10-13. https://www.electricaltestingreference.com/glossary/dielectric-absorption-ratio/rev/1/.
Electrical Testing Reference, Dielectric absorption ratio (rev. 1, Oct. 13, 2026), https://www.electricaltestingreference.com/glossary/dielectric-absorption-ratio/rev/1/.
@misc{etr-glossary-dielectric-absorption-ratio-rev1,
  title = {Dielectric absorption ratio},
  howpublished = {\url{https://www.electricaltestingreference.com/glossary/dielectric-absorption-ratio/rev/1/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {Revision 1; last substantive change 2026-10-13}
}
{{cite web |title=Dielectric absorption ratio |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/glossary/dielectric-absorption-ratio/rev/1/ |date=2026-10-13 |access-date= |version=1}}