Cable Tan Delta

Updated 2026-10-13

RelationshipsCable Tan Delta is governed by ANSI/NETA ATS-2025, ANSI/NETA MTS-2023 and applies to no listed equipment.ANSI/NETA ATS-2025 Standard for Acceptance Testing SpecificationsANSI/NETA ATS-2025ANSI/NETA MTS-2023 Standard for Maintenance Testing SpecificationsANSI/NETA MTS-2023Cable Tan DeltaCable Tan Delta
Relationships. Governing standards on the left, equipment classes the test applies to on the right, as recorded for this entry.
Relationships: relationships recorded for this entry.
RelationshipEntry
Governing standardANSI/NETA ATS-2025 (ANSI/NETA ATS-2025 Standard for Acceptance Testing Specifications)
Governing standardANSI/NETA MTS-2023 (ANSI/NETA MTS-2023 Standard for Maintenance Testing Specifications)

Data records

Sources

  • ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 7.3.3.B.6. Held as: Purchased single-user copy. Publisher page for ANSI/NETA ATS-2025Publisher information page
  • ANSI/NETA MTS-2023, Maintenance Testing Specifications for Electrical Power Equipment and Systems, 2023 edition, NETA. Cited: clause 7.3.3.B.7. Held as: Purchased single-user copy. Publisher page for ANSI/NETA MTS-2023Publisher information page
  • Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.

Also stated in

  • Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-29.c, PDF page 84, printed 5-17, the ellipsis drops the lead sentence of the list and the first two sentences of item (1) (29 November 1996).
    Read the reference passage

    5-29.c. Effectiveness of power factor tests

    "This test can be performed at any voltage that does not exceed the line-to-ground voltage rating of the cable. [...] The shield should be grounded for the test only at the end where the test connections are made. An increase in power factor can indicate discontinuities or breaks in the shield."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-29.c, PDF page 84, printed 5-17, the ellipsis drops the lead sentence of the list and the first two sentences of item (1), 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

  • Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-29.d, PDF page 84, printed 5-17, the first sentence of the paragraph (power factor independent of voltage) is left out (29 November 1996).
    Read the reference passage

    5-29.d. Power factor tip-up testing

    "An increase in power factor at an increased test voltage is usually an indication of insulation voids. These voids are ionized at the higher voltage and act as resistors resulting in a greater resistive current and therefore a greater power factor. This increase in voltage is called power factor tip-up test. (1) Two to five measurements should be made at voltages with an overall 5 to 1 ratio in order to determine whether there are any significant differences in the measured power factors. (2) Generally differences are not a concern unless the higher value exceeds 25 percent of the lower value."

    TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-29.d, PDF page 84, printed 5-17, the first sentence of the paragraph (power factor independent of voltage) is left out, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082

    The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.

Obtaining the documents

Changelog (5 entries)
DateRevisionChange
2026-10-13created (tests.cable-tan-delta.equipment.cable.acceptance)
2026-10-13created (tests.cable-tan-delta.equipment.cable.maintenance)
2026-10-13created (tests.cable-tan-delta.governed-by.ansi-neta-ats)
2026-10-13created (tests.cable-tan-delta.governed-by.ansi-neta-mts)
2026-10-13created (tests.cable-tan-delta.title)

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Cable Tan Delta." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/tests/cable-tan-delta/.
Electrical Testing Reference, Cable Tan Delta (Oct. 13, 2026), https://www.electricaltestingreference.com/tests/cable-tan-delta/.
@misc{etr-tests-cable-tan-delta,
  title = {Cable Tan Delta},
  howpublished = {\url{https://www.electricaltestingreference.com/tests/cable-tan-delta/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {last substantive change 2026-10-13}
}
{{cite web |title=Cable Tan Delta |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/tests/cable-tan-delta/ |date=2026-10-13 |access-date=}}