Contact Resistance
Updated 2026-10-13
| Relationship | Entry |
|---|---|
| Governing standard | ANSI/NETA ATS-2025 (ANSI/NETA ATS-2025 Standard for Acceptance Testing Specifications) |
| Governing standard | ANSI/NETA MTS-2023 (ANSI/NETA MTS-2023 Standard for Maintenance Testing Specifications) |
Data records
- Contact Resistance is specified for automatic transfer switches in emergency systems in acceptance testing at clause 7.22.3.B.4 of ANSI/NETA ATS-2025. Value: automatic transfer switches in emergency systems.
- Contact Resistance is specified for automatic transfer switches in emergency systems in maintenance testing at clause 7.22.3.B.3 of ANSI/NETA MTS-2023. Value: automatic transfer switches in emergency systems.
- Contact Resistance is specified for low-voltage network protectors in acceptance testing at clause 7.8.B.3 of ANSI/NETA ATS-2025. Value: low-voltage network protectors.
- Contact Resistance is specified for low-voltage network protectors in maintenance testing at clause 7.8.B.3 of ANSI/NETA MTS-2023. Value: low-voltage network protectors.
- Contact Resistance is specified for oil automatic line sectionalizers in acceptance testing at clause 7.24.2.B.3 of ANSI/NETA ATS-2025. Value: oil automatic line sectionalizers.
- Contact Resistance is specified for oil automatic line sectionalizers in maintenance testing at clause 7.24.2.B.3 of ANSI/NETA MTS-2023. Value: oil automatic line sectionalizers.
- Contact Resistance is addressed in ANSI/NETA ATS-2025.
- Contact Resistance is addressed in ANSI/NETA MTS-2023.
- The test method is named Contact Resistance. Value: Contact Resistance.
Elsewhere in the family
- Contact Resistance more on this entry on Circuit Breaker Reference
- Contact Resistance more on this entry on Motor Testing Reference
- Contact Resistance more on this entry on Switchgear Testing Reference
- Dynamic Contact Resistance related entry on Circuit Breaker Reference
- Battery Intercell Connection Resistance related entry on Battery Testing Reference
- Battery Internal Ohmic Measurement related entry on Battery Testing Reference
- Contact resistance related entry on Test Instrument Reference
- Low-resistance ohmmeter related entry on Test Instrument Reference
Sources
- ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 7.22.3.B.4; clause 7.8.B.3; clause 7.24.2.B.3. Held as: Purchased single-user copy. Publisher page for ANSI/NETA ATS-2025Publisher information page
- ANSI/NETA MTS-2023, Maintenance Testing Specifications for Electrical Power Equipment and Systems, 2023 edition, NETA. Cited: clause 7.22.3.B.3; clause 7.8.B.3; clause 7.24.2.B.3. Held as: Purchased single-user copy. Publisher page for ANSI/NETA MTS-2023Publisher information page
- Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
Also stated in
- FIST 4-7, section 6.1.10.1, pages 43 to 44 (August 2023).
Read the reference passage
6.1.10.1 Contact Resistance Test
"When draw-out type circuit breakers are provided, contact resistance measurements should be conducted with the breaker removed from its cubicle fully isolated from energized circuits ideally placed on a sturdy work bench or cart. The breaker should be cycled open and closed a few times to verify the repeatability of contact resistance and to work lubricants in the operating mechanism. Note that contact grease should not be applied to arcing contacts, otherwise arcing contact resistance may increase over time."
FIST 4-7, section 6.1.10.1, pages 43 to 44, August 2023. Agency copy of FIST 4-7
The current standard governs; this passage is a public-domain description of the practice dated August 2023.
Obtaining the documents
- ANSI/NETA ATS-2025: available from the publisher
- ANSI/NETA MTS-2023: available from the publisher
Changelog (11 entries)
| Date | Revision | Change |
|---|---|---|
| 2026-10-13 | created (tests.contact-resistance.equipment.ats-transfer.acceptance) | |
| 2026-10-13 | created (tests.contact-resistance.equipment.ats-transfer.maintenance) | |
| 2026-10-13 | created (tests.contact-resistance.equipment.network-protector.acceptance) | |
| 2026-10-13 | edited (tests.contact-resistance.equipment.network-protector.acceptance) | |
| 2026-10-13 | created (tests.contact-resistance.equipment.network-protector.maintenance) | |
| 2026-10-13 | edited (tests.contact-resistance.equipment.network-protector.maintenance) | |
| 2026-10-13 | created (tests.contact-resistance.equipment.sectionalizer.acceptance) | |
| 2026-10-13 | created (tests.contact-resistance.equipment.sectionalizer.maintenance) | |
| 2026-10-13 | created (tests.contact-resistance.governed-by.ansi-neta-ats) | |
| 2026-10-13 | created (tests.contact-resistance.governed-by.ansi-neta-mts) | |
| 2026-10-13 | created (tests.contact-resistance.title) |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Contact Resistance." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/tests/contact-resistance/.
Electrical Testing Reference, Contact Resistance (Oct. 13, 2026), https://www.electricaltestingreference.com/tests/contact-resistance/.
@misc{etr-tests-contact-resistance,
title = {Contact Resistance},
howpublished = {\url{https://www.electricaltestingreference.com/tests/contact-resistance/}},
organization = {Electrical Testing Reference},
publisher = {Electrical Testing Reference},
year = {2026},
note = {last substantive change 2026-10-13}
}{{cite web |title=Contact Resistance |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/tests/contact-resistance/ |date=2026-10-13 |access-date=}}