DC System Ground Detection

Updated 2026-10-13

RelationshipsDC System Ground Detection is governed by ANSI/NETA ATS-2025, ANSI/NETA MTS-2023, NEMA PE 5-1997 (R2003) and applies to no listed equipment.ANSI/NETA ATS-2025 Standard for Acceptance Testing SpecificationsANSI/NETA ATS-2025ANSI/NETA MTS-2023 Standard for Maintenance Testing SpecificationsANSI/NETA MTS-2023Utility-Type Battery ChargersNEMA PE 5-1997 (R2003)DC System Ground DetectionDC System Ground Detection
Relationships. Governing standards on the left, equipment classes the test applies to on the right, as recorded for this entry.
Relationships: relationships recorded for this entry.
RelationshipEntry
Governing standardANSI/NETA ATS-2025 (ANSI/NETA ATS-2025 Standard for Acceptance Testing Specifications)
Governing standardANSI/NETA MTS-2023 (ANSI/NETA MTS-2023 Standard for Maintenance Testing Specifications)
Governing standardNEMA PE 5-1997 (R2003) (Utility-Type Battery Chargers)

Data records

Sources

Also stated in

  • FIST 4-7, section 6.1.20.1, page 64 (August 2023).
    Read the reference passage

    6.1.20.1 Ground Isolation Test

    "The dc distribution centers, and main power cables should be tested for insulation resistance before connection of the battery and charger. Once all of the main power interconnections are made, the complete system should be checked for voltage balance with respect to ground. This verifies that the dc power system is properly isolated from ground before the branch circuits are energized."

    FIST 4-7, section 6.1.20.1, page 64, August 2023. Agency copy of FIST 4-7

    The current standard governs; this passage is a public-domain description of the practice dated August 2023.

  • FIST 3-6, section 9.1, page 95 (April 2020).
    Read the reference passage

    9.1 General

    "DC systems in Reclamation are typically grounded or ungrounded depending on their application. Positive ground DC systems are often implemented on telecommunication systems (typically 48VDC) to provide cathodic protection to buried wires. Wireless communication equipment (typically 24 or 48 VDC) often utilize a negative ground. Ground faults on these grounded systems will be detected by DC overcurrent protective devices."

    FIST 3-6, section 9.1, page 95, April 2020. Agency copy of FIST 3-6

    The current standard governs; this passage is a public-domain description of the practice dated April 2020.

  • FIST 4-7, section 6.1.19.1, page 63 (August 2023).
    Read the reference passage

    6.1.19.1 Polarity (DC) Test

    "Readings between the positive and negative lead of a battery system or power supply should yield the full rated voltage, for example 24 Vdc or 125 Vdc. However, as most Reclamation dc power sources are floating, a reading of the positive or negative lead to ground can produce varying results."

    FIST 4-7, section 6.1.19.1, page 63, August 2023. Agency copy of FIST 4-7

    The current standard governs; this passage is a public-domain description of the practice dated August 2023.

Obtaining the documents

Changelog (5 entries)
DateRevisionChange
2026-10-13created (tests.dc-system-ground-detection.equipment.solar.acceptance)
2026-10-13created (tests.dc-system-ground-detection.governed-by.ansi-neta-ats)
2026-10-13created (tests.dc-system-ground-detection.governed-by.ansi-neta-mts)
2026-10-13created (tests.dc-system-ground-detection.governed-by.ieee-946)
2026-10-13created (tests.dc-system-ground-detection.title)

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"DC System Ground Detection." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/tests/dc-system-ground-detection/.
Electrical Testing Reference, DC System Ground Detection (Oct. 13, 2026), https://www.electricaltestingreference.com/tests/dc-system-ground-detection/.
@misc{etr-tests-dc-system-ground-detection,
  title = {DC System Ground Detection},
  howpublished = {\url{https://www.electricaltestingreference.com/tests/dc-system-ground-detection/}},
  organization = {Electrical Testing Reference},
  publisher = {Electrical Testing Reference},
  year = {2026},
  note = {last substantive change 2026-10-13}
}
{{cite web |title=DC System Ground Detection |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/tests/dc-system-ground-detection/ |date=2026-10-13 |access-date=}}