Continuity and Shield Continuity
Updated 2026-10-13
| Relationship | Entry |
|---|---|
| Governing standard | ANSI/NETA ATS-2025 (ANSI/NETA ATS-2025 Standard for Acceptance Testing Specifications) |
| Governing standard | ANSI/NETA MTS-2023 (ANSI/NETA MTS-2023 Standard for Maintenance Testing Specifications) |
Data records
- Continuity and Shield Continuity is specified for low-voltage cables in acceptance testing at clause 7.3.2.B.2 of ANSI/NETA ATS-2025. Value: low-voltage cables.
- Continuity and Shield Continuity is specified for shielded medium-voltage and high-voltage cables in maintenance testing at clause 7.3.3.B.3 of ANSI/NETA MTS-2023. Value: shielded medium-voltage and high-voltage cables.
- Continuity and Shield Continuity is addressed in ANSI/NETA ATS-2025.
- Continuity and Shield Continuity is addressed in ANSI/NETA MTS-2023.
- The test method is named Continuity and Shield Continuity. Value: Continuity and Shield Continuity.
Elsewhere in the family
- Battery Intercell Connection Resistance related entry on Battery Testing Reference
- Battery Internal Ohmic Measurement related entry on Battery Testing Reference
- Time-domain reflectometer (TDR) related entry on Test Instrument Reference
Sources
- ANSI/NETA ATS-2025, Acceptance Testing Specifications for Electrical Power Equipment and Systems, 2025 edition, NETA. Cited: clause 7.3.2.B.2. Held as: Purchased single-user copy. Publisher page for ANSI/NETA ATS-2025Publisher information page
- ANSI/NETA MTS-2023, Maintenance Testing Specifications for Electrical Power Equipment and Systems, 2023 edition, NETA. Cited: clause 7.3.3.B.3. Held as: Purchased single-user copy. Publisher page for ANSI/NETA MTS-2023Publisher information page
- Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
Also stated in
- Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-29.c, PDF page 84, printed 5-17, the ellipsis drops the lead sentence of the list and the first two sentences of item (1) (29 November 1996).
Read the reference passage
5-29.c. Effectiveness of power factor tests
"This test can be performed at any voltage that does not exceed the line-to-ground voltage rating of the cable. [...] The shield should be grounded for the test only at the end where the test connections are made. An increase in power factor can indicate discontinuities or breaks in the shield."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 5-29.c, PDF page 84, printed 5-17, the ellipsis drops the lead sentence of the list and the first two sentences of item (1), 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
Obtaining the documents
- ANSI/NETA ATS-2025: available from the publisher
- ANSI/NETA MTS-2023: available from the publisher
Changelog (6 entries)
| Date | Revision | Change |
|---|---|---|
| 2026-10-13 | created (tests.continuity-and-shield-continuity.equipment.cable.acceptance) | |
| 2026-10-13 | edited (tests.continuity-and-shield-continuity.equipment.cable.acceptance) | |
| 2026-10-13 | created (tests.continuity-and-shield-continuity.equipment.cable.maintenance) | |
| 2026-10-13 | created (tests.continuity-and-shield-continuity.governed-by.ansi-neta-ats) | |
| 2026-10-13 | created (tests.continuity-and-shield-continuity.governed-by.ansi-neta-mts) | |
| 2026-10-13 | created (tests.continuity-and-shield-continuity.title) |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Continuity and Shield Continuity." Electrical Testing Reference. 2026-10-13. https://www.electricaltestingreference.com/tests/continuity-and-shield-continuity/.
Electrical Testing Reference, Continuity and Shield Continuity (Oct. 13, 2026), https://www.electricaltestingreference.com/tests/continuity-and-shield-continuity/.
@misc{etr-tests-continuity-and-shield-continuity,
title = {Continuity and Shield Continuity},
howpublished = {\url{https://www.electricaltestingreference.com/tests/continuity-and-shield-continuity/}},
organization = {Electrical Testing Reference},
publisher = {Electrical Testing Reference},
year = {2026},
note = {last substantive change 2026-10-13}
}{{cite web |title=Continuity and Shield Continuity |website=Electrical Testing Reference |publisher=Electrical Testing Reference |url=https://www.electricaltestingreference.com/tests/continuity-and-shield-continuity/ |date=2026-10-13 |access-date=}}